![TOHO TTM-i4N Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/toho/ttm-i4n/ttm-i4n_user-manual_1124809024.webp)
24
■
PV compensation gain setting /Zero Setting of PV Correction
Character
Name
Description
Initial Value
1
SET1
INP
Setting Mode Selection
Screen
Input Parameter Mode
Settings about Input
3
PVG
PV compensation gain
setting
Setting Range: 0.50–2.00
Setting Unit: Times
1
00
4
PVS
PV compensation zero
setting
Setting Range: -199–999 or -199.9–999.9
Setting Unit: °C or °F
0
●
PV compensation gain setting
[Function]
Multiplies PV (measurement value) of input with the correction value.
[Sample Setting]
In case PV is displayed as 90°C in an environment where the actual temperature is 100°C, PV can still be adjusted to
100°Cby setting the gain of PV correction to 1.11 (times). [Computation formula = 90°C(before PV correction) x 1.11
times = approximately 100°C]