background image

9

9. SPECIFICATIONS

Standards

Certified to the European Standard EN 54-24:2008
Loudspeaker for voice alarm systems 
for fire detection and fire alarm systems
Certification No. 0359-CPD-0108
Certified to the International Standard ISO 7240-24: 2010 Sound-system 
loudspeaker for fire detection and fire alarm systems
In Compliance with the British Standard BS 5839-8: 2008 14.8

Environment Type

Type B (Outdoor applications)

Rated Noise Power

15 W (100 V line and 70 V line)

Rated Impedance

100 V line: 670 

Ω

(15 W), 1 k

Ω

(10 W), 2 k

Ω

(5 W)

70 V line:  330 

Ω

(15 W), 670 

Ω

(7.5 W), 1 k

Ω

(5 W), 2 k

Ω

(2.5 W)

Sensitivity

97 dB (1 W, 1 m at 330 Hz to 3.3 kHz pink noise)
94 dB (1 W, 1 m at 100 Hz to 10 kHz pink noise)
82 dB (1 W, 4 m at 100 Hz to 10 kHz pink noise)

Max.SPL

104 dB (15 W, 1 m at 100 Hz to 10 kHz pink noise)
92 dB (15 W, 4 m at 100 Hz to 10 kHz pink noise)

Frequency Response

150 Hz – 15 kHz

Coverage Angle (–6 dB)

Horizontal: 140° (500 Hz), 90° (1 kHz), 90° (2 kHz), 100° (4 kHz)
Vertical: 

200° (500 Hz), 155° (1 kHz), 90° (2 kHz), 60° (4 kHz)

Speaker Component

12 cm (5") cone-type (treated for splash proof)

Operating Temperature

–20 ºC to +55 ºC (–4 ºF to +131 ºF)

Dust/Water Protection

IP65

Cable Gland

Size: PG 13.5
One cable gland is factory-installed.
For bridge connection, one cable gland can be added.*

Cable Connection

Screw terminal (Steatite), can be bridge-connected

Applicable Cable Size

Outer diameter: 

ø8.0 – ø12.5 mm

Conductor: 

Solid wire or 7-core wire

No bridge connection: 0.8 – 10 mm

2

(AWG18 – 7) for solid wire,

0.8 – 8 mm

2

(AWG18 – 8) for 7-core wire

Bridge connection: 

0.8 – 2.5 mm

2

(AWG18 – 13) for solid wire,

0.8 – 1.5 mm

2

(AWG18 – 15) for 7-core wire

Finish 

Horn, Cover, and Terminal cover: ABS resin, off-white, paint
Bracket: Stainless 

steel

Net: 

Aluminum, gray, paint

Screw: Stainless 

steel

Dimensions 

366 (w) x 230 (h) x 310 (d) mm (14.41" x 9.06" x 12.2")

Weight 

3.0 kg (6.61 lb)

Accessory

Terminal cover ..... 1

Notes

• The design and specifications are subject to change without notice for improvement. 
• The specifications data was measured in an anechoic chamber, according to EN 54-24.
• Reference axis:  Axis is on the center of horn-mouth and perpendicular to the horn-mouth.
• Reference plane: Plane is on the horn-mouth and perpendicular to the reference axis.
• Horizontal plane: Plane is containing the reference axis and perpendicular to the reference plane.

* Suppliable cable gland's part code and name: 525-52-011-70 Cable gland AVC PGB13.5-12 (GRY)

EN 54-24: 2008
11
0359-CPD-0108

0359

Содержание CS-154BS

Страница 1: ...8 7 WIRING DIAGRAM 8 8 FREQUENCY RESPONSE 8 9 SPECIFICATIONS 9 Thank you for purchasing TOA s Wide Range Speaker Please carefully follow the instructions in this manual to ensure long trouble free use of your equipment TABLE OF CONTENTS Traceability Information for Europe EMC directive 2004 108 EC Manufacturer TOA Corporation 7 2 1 Minatojima Nakamachi Chuo ku Kobe Hyogo Japan Authorized represent...

Страница 2: ... personal injury Avoid installing the speaker near seaside or in locations exposed to corrosive gas The speaker or its parts may be subject to corrosion which might cause it to fall or result in personal injury Do not install the speaker in indoor swimming pools or such locations where liquid chemicals are used The parts deteriorate if corroded causing the speaker to fall which could result in per...

Страница 3: ... efficiency weather resistant horn and a high quality sound cone speaker providing clear and highly directional sound reproduction The CS 154BS is equipped with a constant directivity horn 90 horizontal to control sound directivity realizing uniform and clear sound dispersion over a wide area The CS 154BS is certified to the European Standard EN 54 24 2008 and the International Standard ISO 7240 2...

Страница 4: ...5 W 2 5 W Line Voltage Bold figures represent factory preset values 100V LINE 15W 670Ω 10W 1kΩ 5W 2kΩ OFF OFF OFF 2 5W 2kΩ 5W 1kΩ 15W 330Ω OFF 7 5W 670Ω 70V LINE 4 WIRING The terminal cover is not mounted to the speaker unit when shipped from the factory Note To complete speaker installation be sure to attach the terminal cover after finishing cable connections If the unit is left without the term...

Страница 5: ... If loosely tightened water or moisture may get inside the terminal cover Screw Cable gland Screw Terminal cover 4 5 Inside view of the Terminal cover Waterproof gasket Screw Screw Screw Terminal cover Cable gland Screw 4 4 2 When Bridge Connection is Required Step 1 Punch a knockout hole Punch out the knockout on the terminal cover by tapping the center of the knockout with a screwdriver or other...

Страница 6: ...ver Cable gland Waterproof gasket Nut Terminal cover Step 3 Strip the speaker cable jacket Refer to page 4 Step 1 Step 4 Run one each of speaker cables through the cable gland Terminal cover Speaker cables Cable glands Step 5 Connect the speaker cables with the same polarity to each terminal according to the polarity indication at the screw terminal EARTH HOT COM COM HOT EARTH Screw terminal Speak...

Страница 7: ...ngth from wall surface is less than 15 mm 0 59 If the length is increased beyond 15 mm 0 59 the bolt touches the speaker s terminal cover causing the speaker mounting angle to be limited further Within 90 2 5 Less than 15 mm 0 59 40 Step 6 Attach the terminal cover Secure the terminal cover using the 4 supplied screws In this case take care not to pinch the wiring and check that the waterproof gas...

Страница 8: ...tch Matching transformer Thermal fuse 84 C or 183 2 F Shown above is the factory default wiring 272 10 71 310 12 2 366 14 41 51 2 01 2 01 51 236 9 29 3 ø11 0 43 171 5 6 75 144 5 67 230 9 06 37 1 46 172 6 77 Unit mm in 8 FREQUENCY RESPONSE dB 50 20 50 100 500 1 k 5 k 10 k 20 k Hz 90 80 70 60 100 Frequency Response 1 W 4 m ...

Страница 9: ... 131 ºF Dust Water Protection IP65 Cable Gland Size PG 13 5 One cable gland is factory installed For bridge connection one cable gland can be added Cable Connection Screw terminal Steatite can be bridge connected Applicable Cable Size Outer diameter ø8 0 ø12 5 mm Conductor Solid wire or 7 core wire No bridge connection 0 8 10 mm2 AWG18 7 for solid wire 0 8 8 mm2 AWG18 8 for 7 core wire Bridge conn...

Страница 10: ......

Страница 11: ......

Страница 12: ...URL http www toa jp 533 06 246 30 ...