TX7302 Addressable Flashing Beacon Base
Installation & Operation Manual
affect the operation of the next device with conflicted address number if not carefully
arrange the loop addressing.
3.4 Tone Setting
The TX7302 Addressable Flashing Beacon Base has 16 kinds of different alarm tone and a kind
of warning tone. The Tones of it can be change according to the project requirement by a
programming tool. The detailed parameters of different tone are shown in Table 1.
Table 1 Detailed parameters of different tone
1.
Attach the programming tool to 1 and 6 Terminals of Addressable Flashing Beacon Base.
Press “Power” to switch-on the unit.
2.
Switch-on the programmer, then press button “4” to set the desired tone, as shown in figure
16. Write the number of the corresponding tone and click the button “write”. The word
“Success” or “Fail” on the screen means that the success or not of the encoding mode
setting, as shown in figure 17 and figure 18.
3.
Press “Exit” key to go back Main Menu. Press “Power” to switch off the programmer.
Parameter Tone Code
Description
1
01
970Hz
2
02
800Hz / 970Hz @ 2Hz
3
03
800Hz -970Hz @1Hz
4
04
970Hz 1s off / 1s on
5
05
970Hz, 0.5s / 630Hz, 0.5s
6
06
500Hz - 1200Hz×3, 3.5s on / 0.5s off
7
07
2850Hz, 0.5s on / 0.5s off×3 / 1.5s off
8
08
2850Hz 0.4s on, 0.3s off
9
09
550Hz, 0.7s / 1000Hz, 0.33s
10
10
1500Hz -2700Hz @ 3Hz
11
11
2400Hz
12
12
500Hz -1200Hz @ 0.33Hz
13
13
2400Hz -2900Hz @ 9Hz
14
14
2400Hz -2900Hz @ 3Hz [Default]
15
15
800Hz-970Hz @ 3Hz
16
16
500Hz-1200Hz, 3.75s / 0.25s off
17
17
800Hz 1s off / 1s on [Pre-alarm]
4050100452-Rev1.0-0917
TANDA UK
Specifications are subject to change without prior notice
9