Setting procedure
After the
Interlock is set, the Interlock release screen shows “
on
” automatically.
7.5 Preventing Control with Input Errors (Input Circuit Error Alarm)
Description of function
Input circuit error alarm uses two inputs (dual input circuits) and detects errors in the
input circuit from the difference between two inputs.
When the difference between Input 1_Measured input (PV1) and Input 2_Measured
input (PV2 - PV1) exceeds Input circuit error alarm set value, it is considered to be an
input circuit
error and “Input error state” starts.
Determination of input circuit errors
(PV1 + Input circuit error alarm set value) <
PV2 … Input circuit error (high)
(PV1 - Input circuit error alarm set value) >
PV2 … Input circuit error (low)
[Wiring example]
TC input
RTD input
Voltage input
Current input
ILR
ON
ILR
OFF
[Interlock state]
(Several times)
0 0
(Once or twice)
PV/SV monitor
Monitor & SV setting mode
280
.
.
Interlock release
Monitor & SV setting mode
[Interlock release state]
Interlock release
−
−
Compensating
cable
Input 1
Parallel connection
TC
Input 2
−
−
Input 1
Parallel connection
Input 2
Signal
source
−
−
Input 1
Series connction
Input 2
Signal
source
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...