172-65604MA-00 (
PN-COSR
Pneumatic Control Valve) 10 Sep 2014
10
4. Spacer
Installation
If spacing adjustment is necessary
to accommodate installation, install
a spacer on the outlet flange.
The spacer should consist of a
spacer, gaskets, bolts and nuts. Fit
gaskets to both sides of the spacer
between the
PN-COSR-16
outlet
and the pipe flange. Fasten with
bolts and nuts.
Correct
spacer location
Incorrect
spacer location
5. Piping
Support
Install the
PN-COSR-16
,
paying attention to avoid
excessive load, bending and
vibration.
Support the inlet and outlet
pipes securely.
6. Maintenance
Space
Leave sufficient space for maintenance, inspection
and repair.
(Unit: mm (in))
200
(8)
200 (8)
150
(6)
100 (4)
150
(6)
200
(8)
7. Pressure Sensor Installation
(for pressure control)
The length of piping between
the
PN-COSR-16
and the
pressure sensor should be no
more than 5 m (17 ft). If the
piping distance is too great,
pressure loss and delay of
pressure change along this
distance will increase,
resulting in steam flow rate
fluctuations.
PN-COSR
Pressure
Gauge
Pressure
Sensor
>
>
>
>
>
>
>
>
>
>
Straight
pipe
Straight
pipe
15 d or
more
5 d or
more
Distance of
5 m (17 ft) or less
Steam fluctuations at the pressure sensor may impair the stability of the
pressure control. Ensure a straight piping run of at least 15 d upstream and
5 d downstream from the pressure sensor.