172-65134A-03 (NF6) 16 Dec 2019
3
Specifications
Install properly and DO NOT use this product outside the recommended
operating pressure, temperature and other specification ranges.
Improper use may result in such hazards as damage to the product or
malfunctions which may lead to serious accidents. Local regulations
may restrict the use of this product to below the conditions quoted.
CAUTION
Model
Connection
Max. Operating
Pressure
PMO
Max. Operating
Temperature
TMO
Max. Allowable
Pressure*
PMA
Max. Allowable
Temperature*
TMA
Inlet
Outlet
(male)
(female) MPaG (psig)
°C
(°F)
MPaG (psig)
°C
(°F)
NF6
G(PF)
1
/
4
**
R(PT)
1
/
4
G(PF)
1
/
4
**
2.0
(285)
220
(428)
2.0
(285)
220
(428)
Valve Closing Pressure: 0.016 to 0.047 MPaG (2.3 to 6.8 psig)
(Average: approx. 0.03 MPaG (5 psig))
Valve Opening Pressure: 0.012 to 0.026 MPaG (1.7 to 3.8 psig)
(Average: approx.0.02 MPaG (3 psig))
*Maximum allowable pressure (PMA) and maximum allowable temperature (TMA) are
PRESSURE SHELL DESIGN CONDITIONS,
NOT
OPERATING CONDITIONS.
**Equivalent to BSPP
1
/
4
NOTE: For special order products, confirm the details on the drawing, etc., as the specification
may be different from the above.
Configuration
No.
Name
No.
Name
1
Body
5
Coil Spring
2
Valve Seat
6
Screen
3
Valve Disc
7
Gasket*
4
Valve Disc Guide
*Only on NF6 with straight G(PF) thread. NF6 with
tapered R(PT) thread has no gasket
Installation
Install properly and DO NOT use this product outside the recommended
operating pressure, temperature and other specification ranges.
Improper use may result in such hazards as damage to the product or
malfunctions which may lead to serious accidents. Local regulations
may restrict the use of this product to below the conditions quoted.
CAUTION
Take measures to prevent people from coming into direct contact with
product outlets. Failure to do so may result in burns or other injury from
the discharge of fluids.
CAUTION
Do not use excessive force when connecting threaded pipes to the
product. Over-tightening may cause breakage leading to fluid
discharge, which may cause burns or other injury.
CAUTION
Installation, inspection, maintenance, repairs, disassembly, adjustment and valve
opening/closing should be carried out only by trained maintenance personnel.
1. Before installing the non-freeze valve, blow out any piping scraps, dirt and oil
from the piping and steam trap the non-freeze valve is to be installed on.
2. Before installation, be sure to remove any protective seals.