172-65122MA-04 (L BD2) 9 Mar 2017
6
Installation
Install properly and DO NOT use this product outside the recommended
operating pressure, temperature and other specification ranges.
Improper use may result in such hazards as damage to the product or
malfunctions which may lead to serious accidents. Local regulations
may restrict the use of this product to below the conditions quoted.
CAUTION
Take measures to prevent people from coming into direct contact with
product outlets. Failure to do so may result in burns or other injury from
the discharge of fluids.
CAUTION
Installation, inspection, maintenance, repairs, disassembly, adjustment and valve
opening/closing should be carried out only by trained maintenance personnel.
NOTE: For products with socket weld connections, electric weld with a single pass.
As internal parts are not damaged by the welding process if limited to a
single pass, there is no need to remove them before welding.
1. Before installation, be sure to remove all protective seals.
2. Before installing the product, blow out the inlet piping to remove any piping
scraps, dirt and oil. Close the inlet valve after blowdown.
3. Install the product so that the arrow on the body is pointing in the direction of
condensate flow.
4. Horizontal installation is recommended (with the cover facing upwards). Vertical
installation is possible; however there may be a slight increase in the amount of
steam leakage. Do not install in a reverse installation (the trap upside down) or a
sideways installation (trap on its side).
5. For socket weld connections, weld using an arc weld and keep the actual welding
time as brief as possible.
6. Install a condensate outlet valve and outlet piping.
7. Open the inlet and outlet valves and check to make sure that the product
functions properly.
If there is a problem, determine the cause using the “Troubleshooting” section in
this manual.