background image

 

172-65461MA-03  (JH7.5R-B)    18  Nov  2020

 

6

 

Specifications 

 

 

Install properly and DO NOT use this product outside the recommended 
operating pressure, temperature and other specification ranges. 
Improper use may result in such hazards as damage to the product or 
malfunctions which may lead to serious accidents. Local regulations 
may restrict the use of this product to below the conditions quoted.

 

CAUTION 

 

 

 

DO NOT use this product in excess of the maximum operating pressure 
differential; such use could make discharge impossible (blocked).

 

CAUTION 

 

 

 

Use only under conditions in which no freeze-up will occur. Freezing 
may damage the product, leading to fluid discharge, which may cause 
burns or other injury.

 

CAUTION 

 

Refer to the product nameplate for detailed specifications.   

Model

Maximum Allowable
Temperature (TMA)*

Maximum Allowable

Pressure*

Maximum Operating

Temperature

Nominal Diameter

Maximum Differential
Pressure

Valve No.**

Production Lot No.

 

* Maximum allowable pressure (PMA) and maximum allowable temperature (TMA) are PRESSURE 

SHELL DESIGN CONDITIONS, 

NOT

 OPERATING CONDITIONS. 

** Valve No. is displayed for products with options. This item is omitted from the nameplate when there 

are no options.

 

 

Configuration 

 

 

No.  Name 

M*  R* 

 

11  Cover Gasket 

 

 

12  Cover Bolt 

 

 

13  Cover Nut 

 

 

14  Nameplate 

 

 

15 

Screen Holder 
Retainer 

 

 

16  Snap Ring 

 

 

17  Air Vent Case 

 

 

18  Bimetal Plate 

 

 

19  Air Vent Screen 

 

 

20  Air Vent Valve Seat 

 

 

21  Air Vent Valve Plug 

 

 

No. Name 

M*  R*  F*  No.  Name 

M*  R*  22  Snap Ring 

 

 

1  Body 

 

 

 

6  Orifice Plug 

 

 

23 

Air Vent Guide 
Gasket 

 

 

2  Cover 

 

 

 

7  Orifice Plug Gasket 

 

  24  Air Vent Guide 

 

 

3  Float 

 

 

 

8  Screen 

 

  25  Flange/Socket 

 

 

4  Orifice 

 

   

9  Screen Holder 

 

 

26  Drain Plug Gasket 

 

 

5  Orifice Gasket 

 

   

10  Snap Ring 

 

 

27  Drain Plug 

 

 

* Replacement parts are available only in the following kits: 

M = Maintenance Kit; R = Repair Kit; F = Float 

Содержание JH7.5R-B

Страница 1: ...172 65461MA 03 JH7 5R B 18 November 2020 Free Float Steam Trap JH7 5R B Copyright 2020 by TLV CO LTD All rights reserved ...

Страница 2: ...inge less and lever less free float to rapidly automatically and continuously discharge the inflowing condensate that is continuously generated inside the equipment thus preventing the accumulation of condensate and thereby improving the heat transfer efficiency of the equipment In addition the integral bimetal type automatic air vent allows for the rapid release of start up air and thereby reduce...

Страница 3: ...oses a threat of death or serious injury WARNING Indicates that there is a potential threat of death or serious injury CAUTION Indicates that there is a possibility of injury or equipment product damage WARNING NEVER apply direct heat to the float The float may explode due to increased internal pressure causing accidents leading to serious injury or damage to property and equipment CAUTION Install...

Страница 4: ... recommended components when repairing the product and NEVER attempt to modify the product in any way Failure to observe these precautions may result in damage to the product and burns or other injury due to malfunction or the discharge of fluids Use only under conditions in which no freeze up will occur Freezing may damage the product leading to fluid discharge which may cause burns or other inju...

Страница 5: ...to back pressure has a check valve TLV CK been installed 5 Is the inlet pipe as short as possible with as few bends as possible and installed so the liquid will flow naturally down into the trap 6 Has the piping work been done correctly as shown in the figures below Requirement Correct Incorrect Install catchpot with the proper diameter Diameter is too small Make sure the flow of condensate is not...

Страница 6: ...inflowing condensate causes the float to rise due to buoyancy opening the orifice B and allowing condensate to be discharged The air vent valve will remain closed throughout normal operation due to the high operating temperatures 3 Discharge of Large Quantities of Condensate Increases in the condensate inflow rate cause the condensate level in the trap to rise The float consequently rises and enla...

Страница 7: ...owable Temperature TMA Maximum Allowable Pressure Maximum Operating Temperature Nominal Diameter Maximum Differential Pressure Valve No Production Lot No Maximum allowable pressure PMA and maximum allowable temperature TMA are PRESSURE SHELL DESIGN CONDITIONS NOT OPERATING CONDITIONS Valve No is displayed for products with options This item is omitted from the nameplate when there are no options C...

Страница 8: ...ischarge of fluids CAUTION Installation inspection maintenance repairs disassembly adjustment and valve opening closing should be carried out only by trained maintenance personnel 1 Before installation be sure to remove all protective seals 2 Before installing the product open the inlet valve and blow out the piping to remove any piping scraps dirt and oil Close the inlet valve after blowdown 3 In...

Страница 9: ... losses due to steam leakage Normal Condensate is discharged continuously together with flash steam and the sound of flow can be heard If there is very little condensate there is almost no sound of flow Blocked Discharge Impossible No condensate is discharged The trap is quiet and makes no noise and the surface temperature of the trap is low Blowing Live steam continually flows from the outlet and...

Страница 10: ...faces Replace with a new gasket coat surfaces with anti seize Detaching Reattaching the Cover and its Components Part During Disassembly During Reassembly Cover Nut Remove with a socket wrench Consult the table of tightening torques and tighten to the proper torque Cover Remove by lifting up and off Make sure there are no pieces of the old gasket left on the sealing surfaces of the body and cover ...

Страница 11: ...e Orifice Plug Remove with a box wrench Consult the table of tightening torques and tighten to the proper torque Orifice Plug Gasket Remove the gasket and clean sealing surfaces Replace with a new gasket coat surfaces with anti seize Orifice Remove with a box wrench Consult the table of tightening torques and tighten to the proper torque Orifice Gasket Remove the gasket and clean sealing surfaces ...

Страница 12: ...r Retainer Screen Holder Screen Float Cover Gasket Cover Bolt Body Orifice Gasket Orifice Orifice Plug Gasket Orifice Plug Drain Plug Gasket Drain Plug Air Vent Valve Seat Air Vent Case Air Vent Guide Air Vent Valve Plug Air Vent Guide Gasket Bimetal Plate Snap Ring Air Vent Screen Snap Ring ...

Страница 13: ...e affixes the gasket tightly to the plug holder Check to make sure the gasket is not caught in the recesses of the threads 5 Hold the plug holder upside down to make sure that the anti seize makes the gasket stick to the plug holder even when the plug holder is held upside down 6 Screw the plug holder by hand into the product body while making sure that the gasket remains tightly affixed to the ce...

Страница 14: ...ool The trap operating pressure exceeds the maximum specified pressure or whether there is insufficient pressure differential between the trap inlet and outlet Compare specifications and actual operating conditions Steam is discharged or leaks from the outlet blowing steam leakage Build up on the seating surface of the orifice or rust and scale build up beneath the float Clean parts Scratches on t...

Страница 15: ...roper installation use handling etc by other than TLV CO LTD authorized service representatives 2 Malfunctions due to dirt scale rust etc 3 Malfunctions due to improper disassembly and reassembly or inadequate inspection and maintenance by other than TLV CO LTD authorized service representatives 4 Malfunctions due to disasters or forces of nature 5 Accidents or malfunctions due to any other cause ...

Страница 16: ...MA 03 JH7 5R B 18 Nov 2020 15 Options The options shown below are available for this product on request Please compare with the product you received Options for Area A standard with drain plug Without Drain Plug ...

Отзывы: