172-65453MA-06 (JH5RL-P/JH5RH-P) 31 Jul 2017
14
Options
The options shown below are available for this product
on request. Please compare with the product you
received.
Options for Area A
(standard: without drain plug)
With Drain Plug
Options for Area B
(standard: with cover plug)
A pressure-balancing line connector can be attached to the place where the
standard product has the cover plug.
Socket Type
(Model: JH5RL-W, JH5RH-W)
Flange Type
(Model: JH5RL-F, JH5RH-F)
•
In principle, steam traps automatically discharge inflowing condensate. However, if
low-temperature condensate in the piping blocks the trap inlet passage,
displacement inside the piping of steam by condensate is obstructed and
condensate can no longer flow into the trap (steam-locking). Traps only function in
the presence of condensate inflow. A pressure-balancing line prevents the
occurrence of steam-locking.
Install the pressure-balancing line in the following manner:
Example: Heat Exchanger
Attach the pressure-balancing line
to the trap and to either the
equipment or to an area with a
steam space.
Torque
N
⋅
m (lbf·ft)
Distance
Across Flats
mm (in)
35 (26)
21 (
13
/
16
)
(1 N
⋅
m
≈
10 kg
⋅
cm)
Steam
Pressure-balancing Line