background image

 

172-65483MA-03(JH3S-X / JH5SL-X)  31 Jul 2017 

9

 

Maintenance 

 

 

Take measures to prevent people from coming into direct contact with 

product outlets. Failure to do so may result in burns or other injury from 

the discharge of fluids.

 

CAUTION 

 

 

Be sure to use only the recommended components when repairing the 

product, and NEVER attempt to modify the product in any way. Failure to 

observe these precautions may result in damage to the product or burns 

or other injury due to malfunction or the discharge of fluids.

 

CAUTION 

 

Operational Check 

A visual inspection of the following items should be done on a daily basis to 
determine whether the trap is operating properly or has failed. Periodically (at least 
biannually) the operation should also be checked by using diagnostic equipment, 
such as a stethoscope, thermometer, TLV Pocket TrapMan or TrapMan. 

If the trap should fail, it may cause damage to piping and equipment, resulting in 
faulty or low quality products or losses due to steam leakage.   

Normal: 

  Condensate is discharged continuously, together with flash 

steam, and the sound of flow can be heard. If there is very little 
condensate, there is almost no sound of flow. 

Blocked: 
(Discharge Impossible) 

  No condensate is discharged. The trap is quiet and makes no 

noise, and the surface temperature of the trap is low. 

Blowing: 

  Live steam continually flows from the outlet and there is a 

continuous metallic sound.   

Steam Leakage: 

  Live steam is discharged through the trap outlet together with 

condensate, accompanied by a high-pitched sound. 

(When conducting a visual inspection, flash steam is sometimes mistaken for steam leakage. For 
this reason, the use of a steam trap diagnostic instrument – such as TLV TrapMan - in conjunction 
with the visual inspection is highly recommended.) 

 

Flash Steam                          Live Steam Leakage 

 

 

Parts Inspection 

When parts have been removed, or during periodic inspections, use the following 
table to inspect the parts and replace any that are found to be defective. 

Procedure

 

Gaskets: 

 

Check for warping or scratches 

Screen: 

 

Check for clogging or corrosion 

X-element, Air Vent Valve Seat: Check for scratches 
Float: 

 

Check for scratches or dents 

Body Interior: 

 

Check for build-up 

Orifice Opening: 

 

Check for dirt, oil film, wear or scratches

 

 

Clear, slightly 

bluish jet

 

White jet 

containing 

water droplets

 

Содержание JH3S-X

Страница 1: ...172 65483MA 03 JH3S X JH5SL X 31 July 2017 Free Float Steam Trap with X element JH3S X JH5SL X Copyright 2017 by TLV CO LTD All rights reserved ...

Страница 2: ...ture and responds with great accuracy As a result air and the large quantities of condensate created immediately after the start up of operation are quickly discharged thereby greatly reducing start up time and also proving useful in valve operation bypass blowdown labor saving The X element is also sensitive to hot air during operation responding quickly and thus preventing the occurrence of air ...

Страница 3: ...potential threat of death or serious injury CAUTION Indicates that there is a possibility of injury or equipment product damage WARNING NEVER apply direct heat to the float The float may explode due to increased internal pressure causing accidents leading to serious injury or damage to property and equipment CAUTION Install properly and DO NOT use this product outside the recommended operating pre...

Страница 4: ...n damage to the product and burns or other injury due to malfunction or the discharge of fluids Use only under conditions in which no freeze up will occur Freezing may damage the product leading to fluid discharge which may cause burns or other injury Use only under conditions in which no water hammer will occur The impact of water hammer may damage the product leading to fluid discharge which may...

Страница 5: ... to back pressure has a check valve TLV CK been installed 5 Is the inlet pipe as short as possible with as few bends as possible and installed so the liquid will flow naturally down into the trap 6 Has the piping work been done correctly as shown in the figures below Requirement Correct Incorrect Install catchpot with the proper diameter Diameter is too small Make sure the flow of condensate is no...

Страница 6: ... condensate level causes the float to rise due to buoyancy opening the orifice B and allowing condensate to be discharged 3 Hot Air Discharge Should hot air flow into the trap with the steam during normal operation the temperature of the X element drops causing it to momentarily contract and open the air vent valve A which allows for the rapid discharge of the air After the air is discharged and s...

Страница 7: ... other injury CAUTION Refer to the product nameplate for detailed specifications Model Maximum Allowable Temperature TMA Maximum Allowable Pressure Nominal Diameter Maximum Differential Pressure Production Lot No Valve No Maximum Operating Temperature Maximum allowable pressure PMA and maximum allowable temperature TMA are PRESSURE SHELL DESIGN CONDITIONS NOT OPERATING CONDITIONS Valve No is displ...

Страница 8: ... kit R repair kit F float No Name M R F 1 Body 2 Cover 3 Float 4 Orifice 5 Orifice Gasket 6 Orifice Plug 7 Orifice Plug Gasket 8 Float Cover 9 Screen 10 Flange Socket 11 Cover Bolt 12 Cover Nut 13 Cover Gasket 14 Connector 15 Connector Gasket 16 X element Guide 17 X element 18 Spring Clip 19 Air Vent Valve Seat 20 Name Plate ...

Страница 9: ...mbly adjustment and valve opening closing should be carried out only by trained maintenance personnel 1 Before installation be sure to remove all protective seals 2 Before installing the product open the inlet valve and blow out the piping to remove any piping scraps dirt and oil Close the inlet valve after blowdown 3 Install the product so the arrow on the body is pointing in the direction of flo...

Страница 10: ... flash steam and the sound of flow can be heard If there is very little condensate there is almost no sound of flow Blocked Discharge Impossible No condensate is discharged The trap is quiet and makes no noise and the surface temperature of the trap is low Blowing Live steam continually flows from the outlet and there is a continuous metallic sound Steam Leakage Live steam is discharged through th...

Страница 11: ...a new gasket coat surfaces with anti seize Detaching Reattaching the Cover Part During Disassembly During Reassembly Cover Nut Cover Bolt Remove with a socket wrench Consult the table of tightening torques and tighten to the proper torque Cover Remove by lifting up and off Make sure there are no pieces of the old gasket left on the sealing surfaces of the body and cover then reattach lining up the...

Страница 12: ...ket Remove the gasket and clean sealing surfaces Replace with a new gasket coat surfaces with anti seize Orifice Remove with a socket wrench Consult the table of tightening torques and tighten to the proper torque Orifice Gasket Remove the gasket and clean sealing surfaces Replace with a new gasket coat surfaces with anti seize Table of Tightening Torques Part Name Torque Distance Across Flats N m...

Страница 13: ...5SL X 31 Jul 2017 12 Exploded View JH3S X Float Cover Screen Float Body Orifice Gasket Orifice Orifice Plug Gasket Orifice Plug Cover Gasket X element Guide Air Vent Valve Seat X element Spring Clip Connector Cover Cover Bolt ...

Страница 14: ...1 Jul 2017 13 JH5SL X X element Guide Air Vent Valve Seat Cover Nut Cover Float Cover Screen Float Cover Bolt Body Orifice Gasket Orifice Orifice Plug Gasket Orifice Plug Connector Connector Gasket X element Spring Clip Cover Gasket ...

Страница 15: ... the gasket onto the center of the gasket surface of the plug holder making sure the anti seize affixes the gasket tightly to the plug holder Check to make sure the gasket is not caught in the recesses of the threads Hold the plug holder upside down to make sure that the anti seize makes the gasket stick to the plug holder even when the plug holder is held upside down Screw the plug holder by hand...

Страница 16: ...e trap operating pressure exceeds the maximum specified pressure or there is insufficient pressure differential between the trap inlet and outlet Compare specifications and actual operating conditions Steam is discharged or leaks from the outlet blowing steam leakage Build up on the seating surface of the orifice or rust and scale build up beneath the float Clean parts Scratches on the orifice Rep...

Страница 17: ... to improper installation use handling etc by other than TLV CO LTD authorized service representatives 2 Malfunctions due to dirt scale rust etc 3 Malfunctions due to improper disassembly and reassembly or inadequate inspection and maintenance by other than TLV CO LTD authorized service representatives 4 Malfunctions due to disasters or forces of nature 5 Accidents or malfunctions due to any other...

Страница 18: ...closed position 2 Before operating the lock release valve examine the trap outlet and confirm that the trap is functioning properly 3 Operate the lock release valve as follows tools required flat head screwdriver Open Valve Insert the screwdriver into the slot on the top of the element retainer and slowly turn clockwise Do not turn the element retainer past the point at which it stops See charts b...

Страница 19: ...kg cm 2 Differential Pressure kg cm 2 Discharge Capacity kg h Discharge Capacity liter min Differential Pressure MPa Differential Pressure MPa Discharge Capacity lb h Discharge Capacity scfm Differential Pressure psi Differential Pressure psi Capacities are equivalent capacities of standard air 20 C 68 F under atmospheric pressure ...

Страница 20: ...bottom of the gland case See the above table to determine the amount of steam discharge Close Valve Slowly turn clockwise Do not continue turning the needle valve past the point at which it stops 3 If steam should leak from the gland retainer nut or gland case it can be stopped by further tightening the gland retainer nut Do not over tighten otherwise the needle valve may seize and become unworkab...