Installation
Caution
Install properly and DO NOT use this product outside the recommended operating
pressure, temperature and other specification ranges. Improper use may result in such
hazards as damage to the product or malfunctions that may lead to serious accidents. Local
regulations may restrict the use of this product to below the conditions quoted.
Take measures to prevent people from coming into direct contact with product outlets.
Failure to do so may result in burns or other injury from the discharge of fluids.
Installation, inspection, maintenance, repairs, disassembly, adjustment and valve opening/
closing should be carried out only by trained maintenance personnel.
1.
Before installation, be sure to remove all protective seals.
2.
Before installing the product, blow out the inlet piping to remove any piping scraps, dirt
and oil. Close the inlet valve after blowdown.
3.
Install the product vertically with the inlet at the top and the outlet at the bottom within
the allowable inclination as shown below, and with the arrow on the body pointing in the
direction of flow.
4.
Install condensate outlet valve and outlet piping.
5.
The outlet pipe should lead to a safe place such as a drainage vessel, pit, etc. Make sure
the end of the pipe is above the water level, so that dirt and water cannot be sucked up by
vacuum when the system shuts down.
6.
Open the inlet and outlet valves and check to make sure that the product functions
properly.
7.
After steam has passed through the piping, allow the trap to cool by closing the inlet valve
and then further tighten the clamp.
8.
Open the inlet valve again for normal operation.
If there is a problem, determine the cause using the “Troubleshooting” section in this manual.
Tolerance Angle for Installation: 5°
Make sure the product is installed with the raised TLV lettering on the cover horizontal.
10