2

SAMPLE AND REFERENCE PRESSURE CONNECTIONS

PRESSURE SENSING TUBE INSTALLATION LOCATIONS

FOR MECHANICAL DRAFT INSTALLATIONS

The Pressure Sensing Tube should be installed in the cap of a tee or rear of a common
manifold. The tee is necessary so that only static pressure is measured. If the transducer
sensing tube is installed in the side of a vent pipe it will also measure velocity pressure,
giving an incorrect signal back to the Pressure Control. If mounting on the side of the pipe
is unavoidable, the sensing tube should be flush to the interior wall of the vent pipe.
Typically, draft applications should sample at a point in back of the vent connection that is
farthest from the exhaust fan, (See Figure A).

BALANCING 

BAFFLE

SENSING 

TUBING TO MPCI 

AND PSA-1 FAN 

PROVER

BAROMETRIC 

DRAFT CONTROL 

(IF PRESENT)

HEATER FURTHEST 

FROM THE INDUCER

IF POSSIBLE, THE SENSING TUBE SHOULD BE 

LOCATED TWICE THE MANIFOLD DIAMETER 

BEHIND THE HEATER FURTHEST FROM INDUCER.

2D

MINIMUM

D

FIGURE A

Sensing Tube

Application

Sample Location

MPCI Pressure Port

Reference Pressure Location

MPCI Pressure Port

Exhaust

Bottom of Chase

Connect to Negative (-)

Room at Bottom of Chase

Positive (Port Open)

Draft

Rear of Manifold

Connect to Negative (-)

Heater Mechanical Room

Positive (Port Open)

Open Supply 

Mechanical Room

Positive (Port Open)

Adjacent Room

Connect to Negative (-)

Sealed Supply

End of Supply Duct

Connect to Positive (+)

Heater Mechanical Room

Negative (Port Open)

Recommendations based on MPCI Control being installed in the same room as the sample location. If the MPCI is installed in an
adjacent space, pneumatic connections must be made to the open Pressure Ports that are indicated above.

Содержание MPCI

Страница 1: ...TALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUST MENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRI CAL SHOCK CARBON MONOXIDE POISONIN...

Страница 2: ...in the space or duct GENERAL INFORMATION Each MPCI Controller is electrically factory line tested before shipment After opening carton inspect thoroughly for hidden dam age If any damage is found noti...

Страница 3: ...NG TUBING TO MPCI AND PSA 1 FAN PROVER BAROMETRIC DRAFT CONTROL IF PRESENT HEATER FURTHEST FROM THE INDUCER IF POSSIBLE THE SENSING TUBE SHOULD BE LOCATED TWICE THE MANIFOLD DIAMETER BEHIND THE HEATER...

Страница 4: ...oned between the blower inlet and intake opening FOR OPEN MAKE UP AIR APPLICATIONS In Open mode the mechanical room air is sampled and an adjacent space is referenced Referencing an adjacent space wit...

Страница 5: ...ol set point is outside of the PSA 1 operating range 1 Mount the PSA 1 Pressure Switch within 6 feet of the sensing tube location The switch must be mounted in a vertical position so that the sampling...

Страница 6: ...ATION An intercepted call for heat is sensed at terminals A B or 1 2 of the integral UC1 Interlock Control or MAC Series interlock expansion modules The Amber LED of the UC1 will turn on 1 This closes...

Страница 7: ...6...

Страница 8: ...e the UC1 will continue to operate in post purge mode to allow the fan to purge the heater and vent of residual flue gases A factory post purge time is set at 2 minutes and is adjustable up to 16 minu...

Страница 9: ...mper in proper location based on appliance call interlock voltage SEE WARNING 2 IMPORTANT LED 1 AMBER LED 2 BLUE LED 3 GREEN LED 4 RED LED 5 RED LED 6 RED POWER LED DRY 24 V 115 V APPLIANCE INTERLOCK...

Страница 10: ...ayed Any new fault will replace any previous fault 9 ON PRE PURGE SETTINGS SEE PRE PURGE ON PAGE 3 PRIOR TO SETTING 0 Seconds 15 Seconds 30 Seconds 60 Seconds 1 2 1 2 1 2 1 2 0 Seconds 5 Seconds 20 Se...

Страница 11: ...controls The steps listed under each diagram are intended as a supplement to the diagram Wiring colors or designations may vary by manufacturer If you are unable to wire the UC1 as outlined in these i...

Страница 12: ...ng the MPCI external RED light with audible alarm as well as any external alarm or BMS that are wired to the alarm circuit Reconnect the pneumatic tubing to the sampling tube The safety circuit will r...

Страница 13: ...y draft levels remain within the manufacturer s specified range prior to ignition and during operation CHANGING MPCI PRESSURE CONTROL PROGRAM DEFAULTS THE FACTORY PRESET PROGRAM SETTINGS ARE AS FOLLOW...

Страница 14: ...13...

Страница 15: ...d any service agency who performed work on the system Date of original installation and dates any service work was performed Details of the problem as you can best describe them Tjernlund Products Inc...

Отзывы: