HS2 POWER VENTER SPECIFICATIONS

Performance curves

Static pressure (inches H2O) vs CFM (std. air) at selected flue gas temps.

NOTE:  TO ARRIVE AT TOTAL SYSTEM STATIC PRESSURE REFER TO CURVE
AND ADD .38” TO COMPENSATE FOR VENT HOOD AND WIND RESISTANCE.

MODELS AND APPLICATION:

HS2 (Gas or Oil) 

Used as a means of Side Wall Venting gas or
oil appliances which require a Post Purge cycle.
Used also to co-vent multiple heaters within
combined BTU/hr. input listed below (requires
accessory controls).  Includes a Fan Proving
Switch and the UC1 Universal Control for 24V,
115V or “dry contact” actuation.  LED diagnos-
tics and Pre / Post-purge options are standard
with the UC1.

HSUL-2 (Discontinued 8/05)
HS115-2 & HST-2 (Discontinued 7/02)

Replace above models with HS2.

Note:

Tjernlund Products, Inc. reserves the

right to make changes to specifications without
notification. 

1.40

1.20

70°F

300°F

400°F

500°F

1.00

.60

.20

.40

.80

400

350

250

200

300

150

100

CFM (std air)

50

FIGURE 2102018-3

1 1/2

DRIP SHIELD

ADJUSTMENT ROD

DAMPER

4 5/8

3 1/8

1 1/8

11 5/8

3

6 I.D.

8 5/8

6 I.D.

PSC MOTOR

3,000 R.P.M.

FAN PROVER SENSOR

1

3

6 1/8

11

9 1/4

6 1/4

6 I.D.

5 5/8

7 7/8

2 1/4

FAN PROVING PRESSURE SWITCH

ADJUSTABLE DAMPER

TOLERANCE: ±1/8" UNLESS OTHERWISE NOTED

-SIDE VIEW-

-END VIEW-

-PLAN VIEW-

DIA.

VENT

BTU / HR

MAXIMUM PIPE LENGTH

OIL

GAS

 -- 

 -- 
 -- 

 -- 

 -- 

 -- 

67'

 -- 

100'

 -- 

100'

72'

 -- 

100'
100'

 -- 

100'

67'

100'
100'

15'

94'

100'

100'

450,000
500,000
550,000
600,000

600,000

550,000

500,000

450,000

8"

6"

HS2

500° F

400° F

300° F

FIRED

FIRED

AT STACK TEMPERATURE

(FT)

INPUT

PIPE

MODEL

350,000
400,000

100'
100'

100'

100'

100'

100'

400,000

350,000

100'

100'

100'

100'

100'

100'

TJERNLUND PRODUCTS, INC.

1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com

MOTOR ELECTRICAL DATA

Volts

115

Hertz

60

RPM

3300

Watts

224

Amps

1.51

Therm. Prot.

Yes

MOTOR MECHANICAL DATA

DESCRIPTION

Perm. Split Cap

Yes

Open

Yes

Int. Fan Cooled 

Yes

BEARINGS

Type

Sleeve

Material

Sintered Iron

UC1 UNIVERSAL CONTROL

Maximum Power Consumption 1/2 Amp @
120 VAC 50/60 Hz + Venter motor load

Pre-Purge: Options (0,15,30,60 seconds)

Post-Purge: Factory set at 2 minutes
Options (0,30 seconds; 1,2,4,8,16 minutes)

Dimensions: 5” x 8” (2’ electrical whip inc.)

SAFETY / INTERLOCK 

Fan Proving Switch 

5 VDC UC1 board supplied power switched
through Fan Prover.  UC1 burner / gas valve
interlock rated for 1 H.P. @ 120 VAC. 