Fan Selection Table

The Tjernlund Duct Airstat is
used to automatically activate
Duct Booster fans by sensing
positive pressure in a forced
air heating and/or cooling sys-
tem. The single pole, single
throw, snap-acting switch is
activated by a diaphragm with
a factory installed sampling
probe inserted directly into
the duct or plenum.

PS1503 Specifications

Electrical Rating:

15 Amps non-inductive to 277 Volts AC

Electrical Switch:

SPST, N/O, Snap Action Contacts, Non-adjustable

Operating Pressure/Position:

On pressure rise +.05 ± .02" W.C. (Diaphragm Vertical)

Maximum Pressure:

1/2 PSI

Operating Temperature Range:

-40

0

F to 190

0

F

Sampling Probe:

Self-sealing, Factory-mounted probe

Dimensions:

5 1/2" across bracket, 3" high

Duct Airstat Model PS1503

SC-1 Speed Control 

Speed Control turns Duct Fans on and off
and can vary motor RPM. SC-1 is compati-
ble with Duct Airstat (model PS1503) and
can be used with all High Performance M &
P Series and Duct Booster Fan models EA-5,
EF-6, EF-8 and EF-10. (Face plate fits models
EF-6, 8, 10 electrical box.)

Galvanized 
steel, spring-
loaded 
dampers 
prevent backdrafts.
(4", 6" & 8" sizes.)

White 
plastic, 
dual purpose 
grilles with 
mounting collars. 
(4", 6" & 8" sizes.)

Duct Booster

®

Fan Accessories

Typical Applications

115-120V

Duct

Airstat

Duct

Booster

Electronic

Air Cleaner

Electronic

Duct Heater

Humidifier

G-Series 
Supply/Exhaust
Grilles

BD-Series
Backdraft
Damper 

Tjernlund Products also offers:

• Combustion and fresh air In-Forcers™ ensure

adequate combustion air for heating 
equipment or to improve air quality problems.

• Power Venters easily sidewall vent gas, LP and 

oil fired furnaces, water heaters and boilers.

Sidewall

Power

Venters

Combustion
& Fresh Air
In-Forcers

DR-10 Dryer Vent Switch 

Used to automatically activate P-Series Duct
Booster when dryer is in operation. DR-10 is
a positive pressure sensing switch that rec-
ognizes dryer operation and activates the
booster fan from an independent electrical
circuit. Eliminates connections through the
dryer circuit as well as manual systems
which require attention of the operator.
Operating Pressure/Position:
On pressure rise +.05 to +.07" W.C.
(Diaphragm Vertical)

M-Series
P-Series
EA & EF-Series 
DB-2

Bath/Spa

Exhaust

Duct

Boosting

Indoor/Outdoor

Air

Supply/Exhaust

Radon

Mitigation

Office or

Conference Rm

Exhaust/Boost

Dryer

Venting

Breakroom

or Kitchen 

Exhaust

•                                             •               •              • 

•             •               •              •                                             •       

•             

• 

•             •

•                   

Содержание DUCT BOOSTER IN-LINE DUCT FANS 8500380 REV. A 0104

Страница 1: ...c resi dential and commercial installation requirements www tjernlund com 800 255 4208 Residential Commercial by Tjernlund Solve Air Delivery Problems Duct Booster Fans can be installed in existing supply ducts to boost air flow into hard to heat or cool rooms Solve Exhaust Problems Duct Boosters are the efficient economical way to exhaust unwanted heat humidity odors or other air borne contaminat...

Страница 2: ...V 120V 120V 120V 120V 120V 120V 1 70 HP 30 Watt 30 Watt 56 Watt 1 100 HP 1 25 HP 1 15 HP 51A 40A 40A 1 10A 60A 1 30A 2 17A 150 250 150 150 300 400 800 1100 100 220 100 100 250 325 700 1000 95 180 90 90 200 275 600 900 200 275 180 180 325 475 875 1200 1 Table is based on straight metal duct 90 degree elbows are equivalent to 10 feet of straight duct Performance based on 70 degrees F standard air 2 ...

Страница 3: ...ions Dimensions M Series Electrical and Performance Data Dimensions P Series Electrical and Performance Data Model M 4 M 6 M 8 Max Amps 17 74 1 02 Max Watts 19 84 116 Volts 115 115 115 Nom RPM 2950 2700 2600 0 117 257 481 1 8 101 241 444 1 4 86 221 403 3 8 72 197 361 1 2 58 178 319 3 4 143 237 1 99 177 1 1 2 76 Duct Dia 4 6 8 Weight 6 Lbs 9 Lbs 11 Lbs CFM vs Static Pressure Model P 4 P 6 P 8 OD 9 ...

Страница 4: ... Booster Fan models EA 5 EF 6 EF 8 and EF 10 Face plate fits models EF 6 8 10 electrical box Galvanized steel spring loaded dampers prevent backdrafts 4 6 8 sizes White plastic dual purpose grilles with mounting collars 4 6 8 sizes Duct Booster Fan Accessories Typical Applications 115 120V Duct Airstat Duct Booster Electronic Air Cleaner Electronic Duct Heater Humidifier G Series Supply Exhaust Gr...

Отзывы: