TJERNLUND DRYER DUCT BOOSTER LB2 Скачать руководство пользователя страница 6

MAINTENANCE & SERVICE 

The LB2 motor is maintenance free. If the LB2 is acting erratically, perform the calibration procedure as outlined on the previous page.
The fan impeller is designed for particulate handling, however, if cleaning is needed perform the steps below.

CLEANING INSTRUCTIONS

WARNING:

Disconnect Power from the LB2 before servicing.

1. Loosen the electrical box cover screws from the LB2 using a ¼" nut runner to access the housing cover plate stud within the box.
2. Carefully remove sensing tube from inlet pipe by prying loose with a screwdriver, (See Diagram M).
3. Remove the (6) 8-32 nuts from the outside edges of the housing cover plate, (See Diagram N).
4. Carefully remove the Motor / Impeller assembly by lifting the assembly straight off the housing studs, (See Diagram O).
5. Clean the Impeller and Housing
6. Reassemble in the reverse order.
7. Re-calibrate the LB2. See LB2 Calibration Procedure on prior page. 

If you have any questions about your LB2 we suggest that you contact your installer, contractor or service agency. If you require 
technical information contact Tjernlund Products, Inc. at 1-800-255-4208 or visit www.tjernlund.com.

When contacting Tjernlund Products, Inc., please have the following information available:

1. Name and address of installer and service agency.

2. Job code on nameplate, date of original installation and dates any service work was performed.

LB2 TROUBLESHOOTING

IMPORTANT: 

All faults are indicated by the Red LED light or no Lights on Notification Panel. Faults must be investigated as outlined

below and must only be cleared once a thorough investigation of the dryer vent system and dryer has been performed by someone
qualified to do so. Perform LB2 Calibration Procedure on Page 3 to clear any faults once investigation is complete.

NOTIFICATION PANEL HAS NO LIGHTS:

The Notification Panel should always have a Green LED light on in at least a slow flash mode (1/2 second on, 2 seconds off). Do Not
operate the dryer if there is no Green LED. If no lights are illuminated on the Notification Panel for greater than 5 seconds, there is an
issue with the LB2 installation or the LB2. Confirm the LB2 has Power and that the Notification Panel has been installed (Wired) correct-
ly. If the dryer is operating and there is no Green LED on the Notification Panel, stop the dryer immediately and have the vent system
inspected by someone qualified to do so. Contact Tjernlund at 1-800-255-4208 with further questions.

PRESSURE FAULT MODE:  (Red LED flashing)

If at anytime during the calibration or operating cycle of the LB2 and the Dryer there is excessive positive pressure of +0.16” W.C.
sensed for over four minutes, the Notification Panel will flash the Red LED. Stop the dryer immediately and have the vent system
inspected by a qualified person. This is an indication of excessive back pressure in the vent system. Verify LB2 is located per Minimum
Distance Chart From Dryer on page 1. Move LB2 futher away from dryer if necessary. Make sure termination hood flapper opens.
Check for blockage in vent between LB2 and hood. Verify the LB2 motor is coming on when the dryer turns on. If the motor is not turn-
ing on, make sure the dryer and vent is completely cool and perform the LB2 Calibration Procedure on Page 3. If motor still does not
turn on after being recalibrated, remove power from the LB2 and remove the RED leads from thermal fuse and check for continuity
across the thermal fuse, if open replace fuse and inspect dryer vent system and dryer thoroughly for signs of vent blockage and high

DIAGRAM M

DIAGRAM N

DIAGRAM O

CAREFULLY REMOVE SENSING TUBE
FROM INLET PIPE BY PRYING LOOSE WITH
A SCREWDRIVER UNDERNEATH TUBING.

REMOVE (6) 8-32 NUTS FROM OUTSIDE
EDGES OF MOTOR / IMPELLER ASSEMBLY.

CAREFULLY REMOVE MOTOR /
IMPELLER ASSEMBLY.

5

Содержание DRYER DUCT BOOSTER LB2

Страница 1: ...O 7 62 METERS 25 FT ATTENTION NE PAS INSTALLER DANS UN CONDUIT D ÉVACUATION MESURANT 7 62 MÈTRES 25 PI DE LONGUEUR OU MOINS The Dryer Booster Fan must be accessible after the installation is completed This Dryer Booster Fan may not be used in conjunction with dryers designated as high output WARNING If a blinking or solid Red LED is displayed on the Notification Panel turn off clothes dryer and re...

Страница 2: ...nd 140 F 29 C and 60 C and ambient humidity does not exceed 85 relative humidity Do not install the LB2 in a position where dryer exhaust temperatures exceed 175 F 80 C at LB2 inlet LB2 thermal fuse is set at 186 196 F 86 91 C The dryer duct in which the LB2 is installed must terminate with a dryer vent hood with a damper MINIMUM AND MAXIMUM DRYER DUCT LENGTH IN EQUIVALENT FEET This product is int...

Страница 3: ...between the Notification Panel and the Dryer Duct Booster is greater than the length of the cable splice a section of 3 conductor PVC sheathed 19 AWG or larger 105 degree C thermostat cable to the supplied cable Make sure the color coded leads remain consistent An NEC approved accessible junction box and cover must be used to contain the splice Splices shall be made mechanically secure and insulat...

Страница 4: ...ply Power to the LB2 by plugging in the power cord or cycling the power circuit the LB2 is plugged into NOTE Within 45 seconds of the LB2 Dryer Booster being supplied power it will come on and run for up to 45 seconds This is a cali bration period and will only happen when the LB2 is first powered During this time the Red and Green LED s on the Notification Panel will both flash quickly in an alte...

Страница 5: ...ification Panel has been installed Wired cor rectly If the dryer is operating and there is no Green LED on the Notification Panel stop the dryer immediately and have the vent system inspected by someone qualified to do so Contact Tjernlund at 1 800 255 4208 with further questions See LB2 Troubleshooting for complete details LB2 ELECTRICAL BOX COMPONENTS LB2 ELECTRICAL BOX WIRING CONNECTIONS INSTAL...

Страница 6: ...ION PANEL HAS NO LIGHTS The Notification Panel should always have a Green LED light on in at least a slow flash mode 1 2 second on 2 seconds off Do Not operate the dryer if there is no Green LED If no lights are illuminated on the Notification Panel for greater than 5 seconds there is an issue with the LB2 installation or the LB2 Confirm the LB2 has Power and that the Notification Panel has been i...

Страница 7: ...RANTY Some states do not allow limitation on how long an implied warranty lasts so that limitation may not apply to you In addition some states do not allow the exclusion or limitation of incidental or consequential damages so that above limitation or exclusion may not apply to you This war ranty gives you specific legal rights and you may also have other rights which may vary from State to State ...