Control switch wiring diagram.

Before installation and commissioning you will need:

•  WHR180 or WHR350 manufacturer’s installation and user instructions.
•  Titon ventilation system design specification and parts list.
•  A copy of Standard Assessment Procedure 2005 - Appendix Q - MVHR Installation Guide
   (available from 

www.sap-appendixq.org.uk/documents/MVHR_Installation_Guide_Final.pdf

).

•  Calibrated cone anemometer or similar airflow measuring device.
•  Tool to lock the room ventilation terminals.

Installation guide

Titon recommend the installation guidance given in Standard Assessment Procedure 2005 - Appendix 
Q of the MVHR Installation Guide is followed; not doing so can lead to problems in commissioning or 
failure of the system to meet the requirements of applicable Building Regulations*.

Commissioning

Note: The instructions included in this commissioning guide are product specific and take precedence 
over some parts of Section 2: Commissioning Guidance of Appendix Q MVHR Installation Guide.

Before switching the unit on for the first time ensure that all ventilation terminals (extract and input) 
are fully open and the unit filters are present and clean.

To turn on unit press “

OK

” and “

+

” simultaneously

 

WHR180 & WHR350 - Installation and Commissioning Guide

The fan speeds of the WHR180 and WHR350 are factory set to 75 (program 1) and 100 (program 2).
These must be modified in accordance with the Titon system design specification. 

a

Speed Setting Control Switch Position

b

Speed Setting

Modifying fan speeds

Step 1

 - Select fan speed that requires modification.

•  Press 

F

 for 3 seconds to activate ‘settings menu’.

•  Use 

+

 to select desired parameter.

Step 2

 - Set fan speed, refer to the Titon system design specification for fan speed values.

•  Press 

OK

 for 1 second to display the fan speed value.

•  Modify fan speed value using the 

+

 or 

.

User 

Setting

Speed Setting

1

Setting 1

2

Setting 2

3

Not Used

4

Not Used

5

Not Used

Press 

F

 for 3 seconds to 

activate ‘settings menu’

Use 

+

 to select desired 

parameter

Press 

OK

 for 1 second 

to display the fan speed 

value

Modify fan speed value 

using the 

+

 or 

-

BM813_WHR_installation_instructi2   2