17
Commissioning
TP300A & 301A
The fan speeds of the Titon CME1
Q Plus
will require adjustment to ensure that the
flow rates achieved provide adequate ventilation. The Titon CME1
Q Plus
has 3
standard fan speed settings, Continuous Speed, Boost Speed and Setback Speed.
The Continuous Speed and Boost Speeds are adjustable via Rotary Potentiometers.
Setback Speed is automatically set at the mid point between minimum possible
Continuous Speed and the selected Continuous Speed.
Prior to the first commission, set the Continuous Speed potentiometer to minimum
by rotating fully anti-clockwise and set the Boost Speed potentiometer to maximum
by rotating fully clockwise.
Control Parameters
All volt-free switch inputs are disabled when the Program / Run Header Link is
in the Program position.
All speed control potentiometers are disabled when the Program / Run Header
Link is in the Run position.
The unit needs to be powered up for the commissioning settings to be stored.
Continuous Speed
Boost Speed
Boost Overrun Timer
Program / Run Header Link
1
2
3
4
5
6
7
8
0
30
15
Continuous Speed
Boost Speed
Boost Overrun Timer
Program / Run Header Link
1
2
3
4
5
6
7
8
0
30
15
Control Identification