ventilation systems

Extract Ventilation Unit  

Product Manual

EN

CME1 

Q Plus

TP300A

TP301A

CME1 

Q Plus

with Humidity Sensor

TP300HA

TP301HA

Содержание TP300A

Страница 1: ...ventilation systems Extract Ventilation Unit Product Manual EN CME1 Q Plus TP300A TP301A CME1 Q Plus with Humidity Sensor TP300HA TP301HA...

Страница 2: ...How to Convert Port Cover 13 Wiring Safety 14 Wiring Connections Access 14 Wiring Diagrams 15 Wiring Diagrams 16 Commissioning TP300A 301A 17 Control Parameters 17 Commissioning 18 Boost Overrun 19 C...

Страница 3: ...C x x Humidity levels above 90 or in a wet environment x x The appliance is not suitable for installation to the exterior of the dwelling 4 This appliance is not intended for use by persons including...

Страница 4: ...gram details the overall size of the unit and the additional space required around the unit to allow for commissioning and future servicing and maintenance 450 421 355 390 252 550 450 590 Service Void...

Страница 5: ...5 Component Identification Unit components Cover Inlet ring Scroll Base Cover Scroll Inlet Ring assembly...

Страница 6: ...ivery Check the unit for damage and that all accessories have been supplied The box contains CME1 Q Plus Unit x 1 Port covers x 3 This Product manual x 1 Screw Pack x 1 User Guide x 1 All shortages or...

Страница 7: ...witching can be achieved by use of the Titon Boxed Relay 5A TP 505 The following describes the controls and features of the CME1 Q Plus and how they are controlled Ensure all controls are adequately l...

Страница 8: ...less independent fan control potentiometer Boost Speed with Overrun Timer Boost Speed is an increased speed providing higher extract air flow Boost Speed is configured using a step less independent f...

Страница 9: ...4mm Pan Head screws Always use a fixing type and length suited to the substrate type The unit weighs approximately 5kg 4 Mount the Base ensuring it is not distorted by the fixings or mounting surface...

Страница 10: ...he preformed holes at the front of the Inlet Ring to securely fix the Inlet Ring Scroll assembly to the Base 8 Fit one screw from the Screw Pack through the preformed hole in the back of the Base to s...

Страница 11: ...arp bends in duct work 4 Ducting should be insulated where it passes through unheated areas and voids 5 Unit should be insulated when fitted in unheated area 6 Where a duct extends externally above ro...

Страница 12: ...t be to the external air outside the building envelope 13 All ducting joints including those to the CME1 Q Plus unit s Duct Ports and Convertible Port Covers must be permanently connected and sealed 1...

Страница 13: ...nvert Port Cover 1 To enable fitment of 110 x 54mm ducting modify the Convertible Port Cover by tearing out the rip strip 2 When using the convertible port cover ensure the tear out section is complet...

Страница 14: ...ied persons in order to avoid a hazard 3 The appliance must be connected to a local double pole isolation switch with a contact separation of at least 3mm Ideally located adjacent to the unit 4 CME1 Q...

Страница 15: ...1 Volt free boost switching of unit s controller PCB using single pole switches TP 502 TP 503 TP 507 and or TP500 TP501 Humidistat There is no limit to the number of single pole switches or humidistat...

Страница 16: ...ing inadvertently left in Setback Mode it is recom mended that only one latching switch is fitted Volt free setback switch or normally open relay contacts Setback Switch connection ref EE 152 Three po...

Страница 17: ...t commission set the Continuous Speed potentiometer to minimum by rotating fully anti clockwise and set the Boost Speed potentiometer to maximum by rotating fully clockwise Control Parameters All volt...

Страница 18: ...adjustment potentiometer to achieve required boost air flow 4 Return Program Run Header Link to Run Position fitted to one pin to exit commissioning After commissioning the Program Run Header Link mu...

Страница 19: ...ed and Boost Speed adjustment fully clockwise 3 Place Program Run Header Link in the Program Position 4 Rotate the Continuous Speed adjustment potentiometer fully anti clockwise Hardware Reset Certain...

Страница 20: ...witch inputs are disabled when the Program Run Header Link is in the Program position All speed control potentiometers are disabled when the Program Run Header Link is in the Run position Boost Overru...

Страница 21: ...ent potentiometer to achieve required air flow for each speed 3 Return Program Run Header Link to Run Position fitted to one pin to exit commissioning After commissioning the Program Run Header Link m...

Страница 22: ...to move the Program Run Header Link Humidity Sensor The Humidity Sensor s trigger point is variable from 55 RH to 85 RH Rotate potentiometer to change trigger point Humidity Sensor adjustment can be...

Страница 23: ...e Setback Speed potentiometer fully anti clockwise and the Continuous Speed adjustment potentiometer to the mid position Hardware Reset Certain conditions repeated supply interruptions etc can activat...

Страница 24: ...the system installer WARNING The unit uses a 230V supply and contains rotating mechanical parts ISOLATE the unit from mains power supply and allow sufficient time for all moving parts to stop before u...

Страница 25: ...cleaning 1 Unscrew the 3 retaining screws that hold on the Cover and remove 2 Remove the 4 Scroll retaining screws 3 Using a flat bladed screw driver un clip Scroll from Inlet Ring by disengaging the...

Страница 26: ...nd fan blades using a vacuum cleaner 7 Wipe with damp cloth and mild detergent 8 Check fixing screws 9 Assembly is the reverse of the preceding instructions 10 Ensure all fasteners are secure before r...

Страница 27: ...27 Service Record Serviced by Company Name Date Notes...

Страница 28: ...6 Email ventsales titon co uk Web www titon com 2013 TITON In the event of any queries please contact the system installer Ensure this booklet is passed to the householder once installation and commis...