17
Electro-Pneumatic Positioner
TS600 Series
tissin
2.10.2 TS600R Dimensions
Operation Logic
When the input current (4-20mA) increases, Armature receives counter-clockwise rotating torque as a
magnetic field strength of Torque motor and Flapper moves to left as the center of Plate Spring. When
the space between Flapper and Nozzle opens, the Nozzle back pressure* decreases. As a result,
Exhaust valve of Pilot valve moves to right. At the same time, Supply valve A of OUT1 moves to right
and opens Supply valve. Air supply through OUT1 increases air pressure of diaphragm and
<TS600R Intrinsically safe type / Non-Explosion proof type Dimension>
<TS600R Flame proof type Dimension>
<TS600R Flame proof type Dimension>
<TS600R Flame proof type Dimensio
<TS600R Flame proof type / ATEX & IECEx type Dimension>
Содержание TS600 Series
Страница 13: ...Electro TS600 2 9 2 o Pneumatic Series Parts and 9 1 Stand c Positioner d Assembl dard type r y 13 tissin...
Страница 14: ...14 Electro Pneumatic Positioner TS600 Series tissin 2 9 2 With Position transmitter type...
Страница 16: ...16 Electro Pneumatic Positioner TS600 Series tissin TS600L with Position transmitter type Dimension...
Страница 35: ...35 Electro Pneumatic Positioner TS600 Series tissin Note...