TIS HVAC VAV CONTROLLER

INSTALLATION MANUAL

MODEL: HVAC6-3A-T 

TIS CONTROL LIMITED

RM 1502-p9 Easey CommBldg

253-261 Hennessy Rd Wanchai

Hong Kong

TEXAS INTELLIGENT SYSTEM LLC

SUITE# 610. 860 NORTH DOROTHY DR 

RICHARDSON

TX 75081.USA

Copyright © 2020 TIS, All Rights Reserved

TIS Logo is a Registered Trademark of Texas Intelligent System LLC in the 

United States of America. This company takes TIS Control Ltd. in other 

countries. All of the Specifications are subject to change without notice.

w w w . t i s c o n t r o l . c o m

Data Cable

Use screened stranded RS485 data cable 

with four twisted pairs. Configure devices in 

a “Daisy Chain.” 

Do not cut or terminate live data cables.

Electrical Wires

The  installer  should  adequately  consider 

the total current consumption when 

selecting the wires. 

 

Warranty

We provide a warranty as required by law. 

A  hologram  warranty  seal  and  product 

serial number are provided on each device.

Please send the description of the defect 

with Product S/N to our dealer network. 

Read Instructions

We recommend that you read this 

Instruction  Manual  before  installation.   

Safety instructions

Electrical  equipment  should  only  be 

installed  and  fitted  by  electrically  skilled 

persons. 

Failure  to  observe  the  instructions  may 

cause  damage  to  the  device  and  other 

hazards. 

These instructions are an integral part of 

the product and must remain with the end 

customer.

Programming

This device can be tested and programmed 

manually. Advanced programming requires 

TIS  Device  Search  software.  Advanced 

software  programming  knowledge  should 

be  obtained  in  the  advanced  training 

courses. 

Simple Installation

DIN  Rail  mount  facilitates  installation. 

Fixing  points  are  provided  for  installation 

without  the  use  of  DIN  rail.

Mounting Location

Install in a dry, well-ventilated location. 

Controllers may emit some mechanical 

noises. Consider this when deciding on a 

mounting location.

Содержание T-3A-HVAC6

Страница 1: ...oltage Number of channels 6 Nominal voltage 0 230 V AC 50 60 Hz VAV outputs 0 10V 50mA Output switching current Nominal current per channel Low current 3 A VDC Air condition controllers 2 A VAC Max sw...

Страница 2: ...hologram warranty seal and product serial number are provided on each device Please send the description of the defect with Product S N to our dealer network Read Instructions We recommend that you re...

Страница 3: ...w t i s c o n t r o l c o m Turn off the main electrical source before installation 1 WARNING HIGH VOLTAGE Mount the device on a DIN Rail inside an approved enclosure The device can also be installed...

Страница 4: ...DIUM HIGH Connect to 220 24V AC Second stage Cooling OR Second stage Heating 1 5 mm Electric Cable 2 5 mm Electric Cable GND white orange white brown D white green white blue D blue green 24V brown or...

Страница 5: ...he HVAC as stand alone device without the wall panel thermostat Then connect TIS temperature sensor 2 wires to Temperature sensor terminal in the module low voltage cable low voltage cable GND white o...

Страница 6: ...other thermostat panel and turn the AC ON 2 1 Press the PRG button for 6 seconds until the green LED steady turns on To pair the module to wall panel thermostat complete the following steps manually T...

Страница 7: ...ons are subject to change without notice w w w t i s c o n t r o l c o m DISABLING ENABLING LOCAL OVERRIDE BUTTONS 1 To disable device s local override buttons press on the PRG button for 12 seconds u...

Страница 8: ...e module can get new address Device PRG LED is not Blinking Device not Powered Reason Device is not powered on no TIS BUS 24V supply connected to the device Device Button LED is ON but unit is not res...

Отзывы: