IP GATEWAY WITH RS232/RS485 PORT

TROUBLESHOOTING

PRG Button Blinks Red Color Rapidly 

Reason:

  The  module’s  address  conflicts  with 

another device in the TIS network. You need to 

press and hold the PRG button for 6 seconds so 

that the module can get a new address.

Device PRG LED is not Blinking; 

Device not Powered

Reason:

 Device is not powered on; no TIS-BUS 

24V supply connected to the device.

Device Ethernet LED is not blinking

Reason 1:

 The ethernet cable is not plugged in 

to the module port firmly.   

Reason 2:

 The ethernet cable has a problem or 

is not plugged in to the data switch.

Device Search software can not 

communicate with the module

Reason 1:

  PC  IP  address  is  not  in  the  same 

range  as  the  IP  Module  (192.168.1.xxx). 

Reason 2:

 Device search software was opened 

before  setting  the  PC  IP  address;  you  need  to 

restart  your  software. 

Reason 3:

 If linked by ethernet cable, check the 

connectivity, disable the WiFi on your laptop/PC, 

and restart the software. 

Reason 4:

 TIS software is opened in the same 

PC. Close all TIS software and open just one.

Device Search software can only 

search the IP module but no other TIS 

devices.

Reason:

 Could be a short in connection between 

devices in TIS bus network . 

New IP address in the software could 

not be changed.  

Reason:

 The module is protected. You need to 

press the PRG button for 6 seconds to open the 

protection for 2 minutes so that you can give the 

module a new address. 

TIS app is not able to communicate 

with TIS devices in your local area 

network.

Reason 1:

 Make sure your mobile is on the same 

network as the IP-COM-PORT.

Reason 2:

 In app network settings, you should 

add the Subnet ID, Device ID, and MAC Address 

of the IP-COM-PORT. 

Reason 3:

 Some setting or address is wrong in 

the app.

Содержание IP-COM-PORT

Страница 1: ...N PRODUCT SPECIFICATIONS Ports RS232 RS232 ASCII HEX 2 way connection RS485 Modbus RS485 ASCII HEX 2 way connection RJ45 Ethernet UDP TCP IP connection TIS Bus Number of devices on 1 line Max 64 Bus v...

Страница 2: ...irs Configure devices in a Daisy Chain Do not cut or terminate live data cables Warranty We provide a warranty as required by law A hologram warranty seal and product serial number are provided on eac...

Страница 3: ...GATEWAY WITH RS232 RS485 PORT Turn Off TIS Power supply 1 WARNING HIGH VOLTAGE INSTALLATION STEPS Mount the device on a DIN rail inside an approved enclosure The device can also be installed without t...

Страница 4: ...RNET Connect the IP ethernet cable to the module s RG45 ethernet port CONNECTING TO RS232 3rd PARTY Connect as follows 3rd party device RS232 TX pin to TIS RS232 RX terminal 3rd party device RS232 RX...

Страница 5: ...subject to change without notice w w w t i s c o n t r o l c o m IP GATEWAY WITH RS232 RS485 PORT 24V GND D D 24V D GND RS485 RS232 IP COM PORT D TIS BUS GND PRG Tx Rx D GND 24V D TEMP GND 0 10V T VAV...

Страница 6: ...of the Specifications are subject to change without notice w w w t i s c o n t r o l c o m IP GATEWAY WITH RS232 RS485 PORT TO PAIR THE MODULE TO APPLICATION AS A SERVER GATEWAY PAIRING MANUAL PROGRAM...

Страница 7: ...thout notice w w w t i s c o n t r o l c o m IP GATEWAY WITH RS232 RS485 PORT PAIRING MANUAL PROGRAMMING 24V GND D D 24V D GND RS485 RS232 IP COM PORT D TIS BUS GND PRG Tx Rx D GND 24V D TEMP GND 0 10...

Страница 8: ...ethernet cable has a problem or is not plugged in to the data switch Device Search software can not communicate with the module Reason 1 PC IP address is not in the same range as the IP Module 192 168...