Dimensions: 

 
 

113 mm

101 mm

89 mm

5 mm

13

 mm

5 mm

36

 mm

LED's

Poti

t = 30 mm

 

 
 
 
 

Operating Manual 

 

Mounting Instructions

 

The pin configuration is to be strictly observed. 
The appliance is only to be operated with the 
voltage entered on the rating plate. The metal 
tank and the screening of the connection lines 
are to be safety grounded. The probe- and 
connection lines are not to be laid parallel to 
the drive connections. The amplifier is not to 
be installed on machine components which are 
hot and subjected to strong temperature 
fluctuations. The probe distance to the vessel 
wall must amount at least 30mm. The influence 
of strong suction effect by for example cooling 
glue, can conduct to material fatigue and in 
extreme cases to probe destruction. 
 

Function 

The capacitive level sensor is provided for the 
detection of insulant, solid and non-conducting 
substances. The appliance evaluates the 
capacity modifications 

Δ

C of the probe base 

capacity.  
 

Adjustment/Operation 

The adjustment of the appliance is simply to be 
seen as a tolerance compensation. Resulting 
from installation, filling media and the 
fabrication, tolerances are given, which are so 
compensated. The adjustment occurs, with the 

potentiometer, over the probe sensitivity, and 
must always be made with the effectively used 
filling media. 

In direction of rotation to the right, the level 
increases. In direction of rotation to the left, the 
level decreases. 

In the case of a possible 

defect of the appliance, the exit can take any 
condition on. 
 

Maintenance 

The appliance is maintenance free. Appliances 
are only to be repaired or touched up by the 
manufacturer. 
 

General 

With installation and operation of the capacitive 
level sensor, CNS 506D, the EU- and national 
regulations must be considered. Our 
appliances are on a high technical level. 
Modifications, which serve the technical 
progress, are reserved. 
 

Met standards 

EN 61000-6-2 
EN 61000-6-4 
 

EU-directives 

89/336/EWG 

 

 
 
 
 
 

Tippkemper Elektronik GmbH & Co KG 

Zum Kreuzweg 12, D-59302 Oelde, Germany, Tel. +49 (0) 25 29 / 93 01-50, Fax. +49 (0) 25 29 / 93 01-49 

E-mail: [email protected] 