4. Installation
5. Fuse
Use the appropriate BS 1362 fuse for the load. The unit is supplied with a
suitable 13A fuse.
Fig. 3
Internal Schematic of FST17A / FST11A
The unit is designed to replace an existing single gang connection unit or fixed
appliance outlet giving timed mains output, protected by a BS 1362 fuse. The unit is
capable of forming part of a ring main (the terminals can accept 2 x 2.5mm sq.
cables) or terminating a spur off the ring main. The unit requires a minimum depth of
25mm within the box.
Ensure that the wiring is adequate for the load to be carried. Connect incoming and
outgoing cables to the relevant terminals. Secure the unit to the back box with the
3.5mm screws provided forming the cables during installation to avoid entrapment
and cable damage.
Use the earth terminal in the back box for earth continuity if required. If installed into
a metal back box, earthing of the back box is required.
There is a removable cable blank to cover the front cable exit if this feature is not
required. If front exiting cable is required, for instance to connect to a washing
machine, use the cable clamp supplied to secure the outgoing cable.