TIME MARK A263 Скачать руководство пользователя страница 2

INSTALLATION

 

 

Connect the 3-phase wires to the terminals marked 

A

B

 and 

C

 

The control wiring will be connected to the opposite end of the 
unit, to the terminals with the contact markings.  Markings on 
the unit are the failed condition of the contacts. 

 

AUTOMATIC RESET VERSIONS: 

 

Apply power.  If the contacts do not transfer (TRIP LED-Off), 
check  that  all  three  phases  are  present  and  of  the  correct 
voltage. 

 

If  all  phases  are  correct,  rotate  the  VOLTS  adjustment 
potentiometer counter-clockwise, to the low position. 

 

If the contacts still do not transfer, remove power from the unit.  
Reverse any two of the three input wires and re-apply power.  
The contacts should transfer to the energized condition; N.O. 
contact-closed, NORMAL LED-On. 

 

MANUAL RESET VERSIONS: 

 

Apply power and press the RESET button.  If the contacts do 
not  transfer  (TRIP  LED-Off),  check  that  all  three  phases  are 
present and of the correct voltage. 

 

If  all  phases  are  correct,  rotate  the  VOLTS  adjustment 
potentiometer counter-clockwise, to the low position and press 
the RESET button. 

 

If the contacts still do not transfer, remove power from the unit.  
Reverse any two of the three input wires and re-apply power.  
Press the RESET button.  The contacts should then transfer to 
the  energized  condition;  N.O.  contact-closed,  NORMAL  LED-
On. 

TYPICAL APPLICATION 

MODEL

263

ADJUSTMENT SETTINGS

 

 

NOTE:    During  adjustment,  you  may  wish  to  install  a jumper 
across the control contacts, to prevent cycling the load on and 
off. 

 

AUTOMATIC RESET VERSIONS:

 

 

Rotate  the  VOLTS  adjustment  slowly  clockwise,  until  the 
contacts transfer to the failed condition (TRIP LED-On). 

 

Slowly  turn  the  adjustment  back  counter-clockwise,  until  the 
contacts reset to the normal condition (TRIP LED-Off).

 

 

Remove the jumper, if installed.  This setting will be correct for 
most applications.

 

 

If nuisance tripping occurs, turn the adjustment slightly farther 
counter-clockwise.    In  adjustments  to  eliminate  nuisance 
tripping,  the  VOLTS  adjustment    should  be  rotated  in  very 
small increments, until the true nuisance trips are eliminated. 

 

MANUAL RESET VERSIONS:

 

 

During adjustment, you will need to press and hold the RESET 
button.

 

 

Rotate  the  VOLTS  adjustment  slowly  clockwise,  until  the 
contacts  transfer  to  the  failed  condition  (TRIP  LED-On).    A 
slight buzz in the contacts may occur when the relay is at the 
transfer  point  to  the  failed  condition.    This  is  normal  and  will 
not occur in operation.

 

 

Slowly  turn  the  VOLTS  adjustment  back  counter-clockwise, 
until the contacts reset to the normal condition (NORMAL LED
-On). 

 

Release  the  RESET  button,  and  remove  the  jumper,  if 
installed.  This setting will be correct for most applications.

 

 

If nuisance tripping occurs, turn the adjustment slightly farther 
counter-clockwise.    In  adjustments  to  eliminate  nuisance 
tripping,  the  VOLTS  adjustment    should  be  rotated  in  very 
small increments, until the true nuisance trips are eliminated. 

 

WARRANTY

 

 

This product is warranted to be free from defects in materials 
and  workmanship,  and  is  covered  by  our  exclusive 

5-year 

Unconditional  Warranty

.    Should  this  device  fail  to  operate 

for any reason, we will repair it for five years from the date of 
manufacture.    For  complete  warranty  details,  see  the 

Terms 

and Conditions of Sales

 page in the front section of the Time 

Mark catalog or contact Time Mark at 1-800-862-2875. 

MODEL 263 

3-Phase Monitor

 

READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING  THIS DEVICE. 

KEEP THIS DATA SHEET FOR FUTURE REFERENCE. 

 

GENERAL SAFETY

 

 

POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 263.

 

ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING. 

THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL. 

 

Installation Instructions 

 

TIME MARK is a division of

 

 

 

 

 

 

 

  

 

 

 

 

 

   

 

  

 

11/2011 

© 2011   

TIME MARK CORPORATION

 

 

  

 

Shown De-Energized 