Instructions
2.1
Mounting
The transducer is mounted on a 35mm DIN rail on a wall or device cabinet for suitable
protection. The enclosure shall not be accessible without tools.
2.2
Installation
The installation is to be made by competent personnel and in accordance with
applicable regulations. Before installation please check that the transducer has the
correct type and complies with the installation needs. The connection to the transducer
is done through the terminals that are designed for a maximum of 2 x 2,5 mm² cable in
accordance with connection diagram. An external switch shall be used so that the unit
can be deenergized during disassembly. It shall be appropriately positioned, easy to
reach and marked as a switch for the transducer. The measuring circuits from the
current transformers must be short-circuited before disconnection.
2.3
Operation
The transducer is intended for operation at an altitude not exceeding 2000m and in an
environment that is not considered as wet location.
2.4
Warning!
Connection must comply with current regulations for systems with rated voltage up to
1000 V.
Before switching on or off and if the housing is removed, all voltages to the appliance
must be switched off.
2.5
Maintenance
The transducer requires no maintenance. Any repairs shall be performed by trained
personnel or the appliance shall be returned to the supplier for repair.
Function and safety are only guaranteed if the instructions in this manual are followed.