Modbus protocol profile Mapping 002
The output registry for the measured quantities is updated every 25 ms with profile mapping 002.
adr
format
parameter
explanation
0 binary32 F
Hz
Frequency
system
2 binary32 I
A
Input current
system
I = (I1+I2+I3)/3
4 binary32 I1
A
Phase current
L1
6 binary32 I2
A
Phase current
L2
8 binary32 I3
A
Phase current
L3
10 binary32 U
V
Input voltage
system
U = (U1+U2+U3)/3
12 binary32 U1
V
Phase voltage
L1-N
14 binary32 U2
V
Phase voltage
L2-N
16 binary32 U3
V
Phase voltage
L3-N
18 binary32 U12 V
Main voltage
L1-L2
20 binary32 U23 V
Main voltage
L2-L3
22 binary32 U31 V
Main voltage
L3-L1
24 binary32 P
W
Active power
system
P = P1+P2+P3
26 binary32 Q
var Reactive power
system
Q = Q1+Q2+Q3
Modbus function code 04: Read Input Registers
The data format used is IEEE 754 single-precision binary floating-point format: binary32
Parameters are represented as two consecutive Modbus registers.
The value of a parameter is represented in SI unit as secondary values on transducer input.
To calculate primary values, use the primary to secondary transformer ratio of parameter CTR, PTR
The CTR and PTR parameter can be configured by the user by editing primary to secondary
current- and voltage-ratio in ConfigLQT.