Instruction Manual for Installation and Application of JTW-ZOM-TC5162 Addressable Rate of Rise and Fixed Temperature Heat
Detector
1).Registration: After confirming the installation and wiring is correct, register devices to the fire alarm
control panel, and check whether the numbers of installed detectors and registered detectors are
consistent.
2).Fire simulation test: After registration, choose one detector arbitrarily, and fit it to meet fire conditions
to check whether the detector generates fire normally.
3).After testing, reset the detector. Notify the proper authorities that the system returns to normal state.
4).Clean the failure detector in the test according to Maintenance, and test it again. If it is still fail to pass,
please return it to repair.
3. Do not connect to the power supply before all detectors been installed.
VII Usage and Operation
1 Electronically coding for the detector makes it easy and convenient. TCBM5023 hand-held encoder made
by TC is used for field coding. When coding, connect the encoder with detector loop terminal (non-polarity)
and write or read the address code.
2 Coding step: press “2” in the main menu of the encoder to enter into “(2) mode setup” and choose “(1)
TC5000” in the sub menu. Press “(5), (6), or (7)” to choose ascending number coding, normal coding or
descending number coding. Easy application (default is TC5000, normal coding) and chosen complete, press
“erase/roll page” to enter into coding interface and press exit to return to main page. Press “1” for “(1) write
address” and connect the encoder with the detector loop terminal L1 and L2. At standby status, input
detector address (1 to 255) and press “write address”. “OK” means write-in success and “fail” means not.
VIII Fault and maintenance
4. Wrong address
Check whether
Hand-Held Encoder
works normally, and whether battery discharge. Check whether
connection is correct, or there is a fault in circuit.
5. Cannot register
Check whether loop connection is correct, and loop voltage is 18-24V in normal. Plug firmly or there is a
fault in circuit.
6. Report fault
Read code with
Hand-Held Encider,
if code is correct in a state of polarity intermodulation, the detector
works normally. And then check connection or there is a fault in circuit.
4. False alarm
5