SETTING AND COMMISSIONING
54
NA016 - Manual - 05 - 2022
Store
command, located in the “Set” menu has been used; in this regard, once the “
Store
” mes-
sage is displayed, it is necessary to use the
Enter
button; this results in the “
execute
” message
with the symbol “
C
” flashing.
• Browse the menu by means of the
Left
and
Up
or
Down
keys to go in the
Store
menu.
• Press the
Enter
button; once more concludes the save procedure with the temporary appearance
of the message “
ok
!”.
After one or more modifications, the status of having data that has still not been permanently saved
is indicated by the “
!
” symbol in the top right and the display message “
WARNING set Clear..
Store
” which appears while browsing through the main menu with the use of the
Up
or
Down
keys.
• The Clear command may be used to abandon unsaved changes (prior to use of the Store com-
mand); the same effect is achieved by switching the key to the OFF position or removing the auxil-
iary power supply to the relay.
Example
To set the K1 relay with Energized mode and latched mode (Energized, Latched) the following
sequence must be operated:
• Select the Set menu “
Set >
”by means of the
Down
key.
• Press the
Right
key; the message “
Base >
” is displayed.
• Browse the menus with
Down
“
Relays
>
”
“
50/51
>
”
“
50N/51N
>
”
“
Circuit breaker
>
”
“
Clear
>
”
“
Store
>
”
• Select the “
Relays >
”, menu; the message “
K1 None >
” is displayed.
• Press the
Down
key; the message “
K1 Logic De-energized
” is displayed.
• Press the
Enter
key; the he modification in progress status is highlighted by the symbol “E” flashing
in the upper right area of the display.
• Change the parameter by means the
Up
or
Down
keys; the message “
K1 Logic Energized
” is
displayed.
• Press the
Enter
key; acceptance of the change is indicated by the disappearance of the flashing
“
E
” to be replaced by the symbol “
!
”.
• Press the
Down
key; the message “
K1 mode No-latched
” is displayed.
• Press the
Enter
key; acceptance of the change is indicated by the disappearance of the flashing
“
E
” to be replaced by the symbol “
!
”.
• Change the parameter by means the
Up
(increment) or
Down
(decrement) buttons; the message “
K1
mode Latched
” is displayed.
• Press the
Enter
button; acceptance of the change is indicated by the disappearance of the flashing
“
E
” to be replaced by the symbol “
!
”
• Press the
Left
key and
Up
or
Down
to go inside the
Store
menu.
• Press the
Enter
key; this results in the “
execute ?
” message with the symbol “
C
” flashing.
• Answer with
Enter
key to confirm setting.
The end of the setting sequence is signalled by the “
ok
!” message.
The
Reset
key may be used to abort unsaved changes (prior to use of the Store command); the same
effect is achieved by switching the key to the OFF position or removing the auxiliary power supply to
the NA011 relay.
Test
The operational tests with or without command of the associated output relays may be performed.
Browse the main menu by means the
Up
or
Down
keys until the “
Test
” message is displayed; press
the
Enter
key to enter and subsequently select the test by means of the
Up
or
Down
keys.
• Test I> led
• Test I>> led
• Test I>>> led
• Test IE> led
• Test IE>> led
• Test I> full
• Test I>> full
• Test I>>> full
• Test IE> full
• Test IE>> full