![Thytronic N60-MB2 PRON Series Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/thytronic/n60-mb2-pron-series/n60-mb2-pron-series_user-manual_1113979007.webp)
PRON NA60-MB0
Version 3.50
PRON NA60-MB0 Remote Setting Manual
Page: 7 of 59
2.1.2 BYTE
Description:
Signed variable with 1 byte (8 bit) of information. Range: -128
+127
Relationship with Modbus:
A BYTE data type is always placed in the Least Significant Byte (LSB) of a Modbus Register (DIM=1).
B
00
B
Byte
Modbus
Register
Example:
relationship between the data BYTE whose value is 13 (0x0D) and its Modbus representation:
0D
00
0D
Byte
Modbus
Register
2.1.3 UBYTE
Description:
Unsigned variable with 1 byte (8 bit) of information. Range: 0
+255
Relationship with Modbus:
A BYTE data type is always placed in the Least Significant Byte (LSB) of a Modbus Register (DIM=1).
B
00
B
UByte
Modbus
Register
Example:
relationship between the data BYTE whose value is 13 (0x0D) and its Modbus representation:
0D
00
0D
Byte
Modbus
Register