81
DMC3S - Manual - 08 - 2021
—
Average measures
The average measures (Demand) are calculated as follows:
Fixed mean
I
L1FIX
,
I
L2FIX
,
I
L3FIX
Arithmetic mean of the values
I
L1
,
I
L2
,
I
L3
acquired every 1 s, over a time period
t
FIX
, from 1 to 60 min-
utes, updated at the end of the period itself.
The mean can be reset with the keypad, with the command
Reset average measures
(in the menu
Commands
Thysetter), or via a logical input. The parameter
tFIX
is in the menu
Set \ Average meas-
ures
.
Mobile mean
I
L1ROL
,
I
L2ROL
,
I
L3ROL
The arithmetic mean, in a mobile window of
N.Rol
*
tROL
, of the values
I
L1
,
I
L2
,
I
L3
acquired every
1 s, where T is the length of each subinterval of time
tROL
, from 1 to 60 minutes, and
N.Rol
is the
number of subintervals of time (from 1 to 24), updated at the end of each subinterval. The mean can
be reset with the keypad, with the command
Reset average measures
(in the menu
Commands
Thy-
setter), or via a logical input.
The parameters
tROL
and
N.Rol
are in the menu
Set \ Average measures
.
Maximum
I
L1MAX
,
I
L2MAX
,
I
L3MAX
Maximum value of the arithmetic mean of the values
I
L1
,
I
L2
,
I
L3
acquired every 1 s, over a window
equal to the time subinterval
tROL
(setting shared with Mobile mean), updated at the end of the
subinterval itself.
The mean can be reset with the keypad, with the command
Reset average measures
(in the menu
Commands
Thysetter), or via a logical input.
tROL
is the same parameter as that used for the Mobile mean.
Minimum
I
L1MIN
,
I
L2MIN
,
I
L3MIN
Minimum value of the arithmetic mean of the values
I
L1
,
I
L2
,
I
L3
acquired every 1 s, over a window
equal to the time subinterval
tROL
(setting shared with Mobile mean), updated at the end of the
subinterval itself.
The mean can be reset with the keypad, with the command
Reset average measures
(in the menu
Commands
Thysetter), or via a logical input.
tROL
is the same parameter as that used for the Mobile mean.
—
Oscillographyy
Set trigger
The following parameters in the menu
Oscillography \ Set trigger
are user programmable:
•
Pre-trigger time
and
Post-trigger time
.
• When the parameter
Enable triggers with outputs
is set to
ON
, registration starts when any
protection threshold changes state.
• When the parameter
Trigger with outputs
is set to
ON
, registration starts when one or more
outputs selected in the menu
trigger with outputs
(51AP, 52CH, 80S, KS1-1...6) and
trigger
with DMRIS0 control outputs
(OUTD1-1, OUTD1-2, OUTD2-1, OUTD2-2) change status.
• When the parameter
Enable triggers with inputs
is set to
ON
, registration starts when any
logical input selected in the menu changes state.
- Trigger with inputs
(IN1-1...IN1-6, INC-1...INC-5)
- Trigger with DMRIS01 inputs
(IND1-1...IND1-12)
- Trigger with DMRIS02 inputs
(IND2-1...IND2-12)
• Filling 80% of memory will generate an alarm if the parameter
80% buffer alarm
is set to
ON
.
Set sampled channels
The instantaneous values (
i
L1
,
i
L2
,
i
L3
,
i
E
,
u
L1
,
u
L2
,
u
L3
,
u
E
,
u
AUX
,
i
CBCOIL
,
i
L2C
,
i
L2C
,
u
12
,
u
23
,
u
311
,
u
L41
,
I
SQL1
,
I
Ne
) to be registered can be selected in the menu
Set \ Oscillography \ Set sampled channels
.
Set measurement channels
The analogue values (Frequency,
I
L1
,
I
L2
,
I
L3
,
I
E
,
U
L1
,
U
L2
,
U
L3
,
U
E
,
U
12
,...etc.) to be registered can be
selected in the menu
Set \ Oscillography \ Set measurement channels.
Each of the twelve measurement channels can be mapped to a measurement.
Set digital channels
The I/O signals (52AP, 52CH, 80S, TripMV, KS1-1... KS1-6, KC2-1...KC2-8, KS1-1... KS1-6, IN1-1... IN1-6,
INC-1... INC-5) to be registered cxan be selected in the menu
Set \ Oscillography \ Set digital chan-
nels
.
Set DMRIS0 digital channels
The I/O signals related to the first external DMRIS0 module (IND1-1...IND1-12, OUT1-1, OUT1-2) and
second external DMRIS0 module (IND2-1...IND2-12, OUT2-1, OUT2-2) to be registered can be se-
lected in the menu
Set \ Oscillography \ Set digital channels
and
Set \ Oscillography \ Set DMRIS0
digital channels
.
Each of the sixteen digital channels can be mapped to an I/O signal.
trigger.ai
Oscillograph trigger
Trigger
Time
pre-trigger
post-trigger
Содержание DMC3S
Страница 76: ...76 DMC3S Manual 08 2021 EACx fxa dfx dt fxb Ueac EnUeac Ueac EnUeac ULS EnULS UG EnUG UDT EnUDT P EnP EAC Logic...
Страница 105: ...105 DMC3S Manual 08 2021 DMC3S DIMENSIONS front internal and rear views...
Страница 106: ...106 DMC3S Manual 08 2021 DMC3S DIMENSIONS viewed from above...
Страница 107: ...107 DMC3S Manual 08 2021 DMC3S DIMENSIONS DMRIS0 module...