Thunderstone Thunder 6000XR Скачать руководство пользователя страница 2

Thunder 6000

XR

 Troubleshooting Guide – 9/1/17

 

 

 

b)

 

Four flashes indicates an Over Voltage Protection issue. Using a voltmeter, check the tractor batteries & 
alternator for voltage exceeding 15.5 volts. 

c)

 

Five flashes indicates an Under Voltage Protection issue. Using a voltmeter, check the system for low 
voltage. Also check all connection points for looseness and corrosion including battery terminals, circuit 
breaker, power cord, and receptacle plug. Connect an alternate power source to verify. 

d)

 

Six flashes indicates Ground Fault Protection. This can be caused by moisture intrusion to the inner control 
box,  motor  terminals  shorted  to  the  motor  case,  and  also  wire  insulation  damage.  To  determine  which 
failure has occurred please follow the steps below: 
(1)

 

If 6 code is intermittent when running the tarp, ground the motor arm to the trailer ladder assembly with 
a jumper wire or a conductive equivalent. This will ensure proper grounding during testing.

 

(2)

 

Remove the motor leads from the motor terminals. Touch the ends together completing the circuit and 

observe if the flashing stops or continues. 

DO NOT OPERATE THE TARP SYSTEM DURING THIS TEST 



If flashing stops, there is a short inside the motor case. Replace the defective tarp 

motor. Test functions before completing installation to verify.

 

(3)

 

If 6 flashes continue after the wires are touched together, inspect the wiring from the inner control 
box to the motor for any frays, pinched areas, or insulation being worn through. Fix or replace any 
areas that show insulation wear or damage. 

(4)

 

Disconnect the large Delphi connector for the motor wires in the nose of the trailer. Insert a paperclip, 
or  conductive  equivalent,  across  the  contacts  in  the  connector  on  the  side  coming  from  the  inner 

control box. Verify if flashing stops. 

DO NOT OPERATE THE TARP SYSTEM DURING THIS TEST 

 

  If flashing stops, there is a ground fault occurring in the wiring to the motor. 

Inspect for damage. Replace cable if necessary. 

(5)

 

If the 6 flashes continue, disassemble the inner control box located in the nose of the trailer and inspect 
for water  intrusion.  Green  corrosion  around  the  amp  control  relay  terminals  is  a  positive  sign of  relay 
failure due to moisture. 



If moisture is present, replace the inner control box. Test functions before re-

installation to verify.

 

e)

 

Seven flashes indicates there is not enough amperage or voltage to run the motor OR the drive motor windings 
are shorted. 

REQUIRES REMOVING POWER TO RESET. 

 

(1)

 

Connect an alternate power source to verify a low amperage/voltage problem.

 

(2)

 

Make sure the charging system on the truck or power supply is running and working properly.

 

 

Replace motor. Test functions to verify.

 

f)

 

Eight flashes indicates com failure from the inner control box. Check com cable between RF keypad and inner 
control box for damage. 

 

 

 



Replace Communication Cable. Test functions before re-installation to verify.

 

 

Tarp system does not make a full cycle or closes/opens intermittently. 

1.

 

Two flashes indicates an overcurrent protection issue which is normal if the tarp fully opened or closed. If not, check 
for obstructions in the operation of the tarp such as snow or ice buildup. This also could indicate increased drag in 
the tarp motor or other motor problems causing premature tarp stoppage. 

2.

 

Remove the motor terminals and connect to a battery source using jumper cables to determine if the motor labors or 
stops with direct current indicating a motor gear mesh issue causing excess drag. 



Replace the tarp motor. Test functions to verify.

 

Отзывы: