1.
General Information
Model L1512D LED luminaires are suitable for use in
the following hazardous (classified) areas as defined
by the National Electrical Code (NEC) and Canadian
Electrical Code (CEC):
l
Class I, Division 1, Groups B, C, D
l
Class I, Division 2, Groups A, B, C, D
l
Class II, Division 1, Groups E, F, G
l
Wet Locations (UL 1598)
Refer to the luminaire nameplate for specific
classification information, maximum ambient
temperature suitability and corresponding operating
temperature (T
-
Code).
Model L1512D LED luminaire is designed for using in
indoors and outdoors environment.
Rated Voltage (DCOB): 120/
277/347/480 Vac,
50 & 60 Hz
Rated Voltage (DOB): 120/
277 Vac,
50 & 60 Hz
Ambient Temperate Range:
-
25°C ~ +40°C (CID1:T5, CID2:T3, CIID1 :T4A)
-
25°C ~ +55°C (CID1:T4A, CID2:T3, CIID1:T4)
WARNING
u
To avoid the risk of fire, explosion or electric shock, this product should be installed, inspected and
maintained by a qualified electrician only, in accordance with all applicable codes and regulations.
u
To avoid electric shock:
ü
Be certain electrical power is OFF before and during installation and maintenance.
ü
Luminaire must be supplied by a wiring system required by the NEC and CEC for the specific
hazardous locations with an equipment grounding conductor.
u
To avoid explosion:
ü
Make sure that the supply voltage is the same as the luminaire voltage.
ü
Do not install where the marked operating temperatures exceed the ignition temperature of the
hazardous atmosphere.
ü
Do not operate in ambient temperatures above those indicated on the luminaire nameplate.
ü
All gasket seals must be clean and undamaged.
ü
Before dismounting, electrical power to the luminaire must be turned off. Keep tightly closed
when in operation.
u
To avoid burning hands, ensure the luminaire is cool when performing maintenance.
u
The internal grounding terminal shall be used as the equipment grounding means and the external
terminal is only a supplemental bonding connection.
u
“WARNING: To prevent ignition of Group B atmospheres conduit runs must have a sealing fitting
connected within 9 inches of the luminaire”.
u
Mounting Orientation
–
Lens horizontal Facing Down or Lens Facing Down 45° from vertical.