1.

General Information

Model L1512D LED luminaires are suitable for use in 
the following hazardous (classified) areas as defined 
by the National Electrical Code (NEC) and Canadian 
Electrical Code (CEC): 

l

Class I, Division 1, Groups B, C, D

l

Class I, Division 2, Groups A, B, C, D

l

Class II, Division 1, Groups E, F, G

l

Wet Locations (UL 1598)

Refer to the luminaire nameplate for specific 
classification information, maximum ambient 
temperature suitability and corresponding operating 
temperature (T

-

Code). 

Model L1512D LED luminaire is designed for using in 
indoors and outdoors environment.

Rated Voltage (DCOB): 120/

277/347/480 Vac,

50 & 60 Hz

Rated Voltage (DOB): 120/

277 Vac,

50 & 60 Hz

Ambient Temperate Range:

-

25°C ~ +40°C (CID1:T5, CID2:T3, CIID1 :T4A)

-

25°C ~ +55°C (CID1:T4A, CID2:T3, CIID1:T4)

 

WARNING

u

To avoid the risk of fire, explosion or electric shock, this product should be installed, inspected and 
maintained by a qualified electrician only, in accordance with all applicable codes and regulations.

u

To avoid electric shock: 

ü

Be certain electrical power is OFF before and during installation and maintenance.

ü

Luminaire  must be  supplied  by a  wiring system required by the NEC and CEC  for the specific 
hazardous locations with an equipment grounding conductor.

u

To avoid explosion:

ü

Make sure that the supply voltage is the same as the luminaire voltage.

ü

Do not install where the marked operating temperatures exceed the ignition temperature of the 
hazardous atmosphere.

ü

Do not operate in ambient temperatures above those indicated on the luminaire nameplate.

ü

All gasket seals must be clean and undamaged.

ü

Before dismounting,  electrical  power  to  the luminaire  must be  turned  off.  Keep  tightly  closed 
when in operation.

u

To avoid burning hands, ensure the luminaire is cool when performing maintenance.

u

The internal grounding terminal shall be used as the equipment grounding means and the external 
terminal is only a supplemental bonding connection.

u

“WARNING: To prevent ignition of Group B atmospheres conduit runs must have a sealing fitting 
connected within 9 inches of the luminaire”.

u

Mounting Orientation 

 Lens horizontal Facing Down or Lens Facing Down 45° from vertical.