![THT-EX L1319 Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/tht-ex/l1319/l1319_operating-instructions_1111698004.webp)
4
6.2 Mounting Bracket Installation
6.2.1
Wall & Hanging Mount Bracket
F
The mount bracket is for the use of both Wall
mount (Figure 1) and Hanging mount (Figure 2).
F
Position the bracket holders and fix it by means of
the provided M8 screws, 61 kgf-cm.
F
Secure the Wall/Hanging mounting bracket to the
structure by using four fasteners
(
not provided).
F
The angle of lighting fixture can be adjusted.
6.2.2
Ceiling Mount
F
The mounting bracket is for the use of Ceiling
mounting.
F
Position the bracket holders and fix it by means of
the provided M6 screws, 24.5 kgf-cm. (Figure 3)
F
Secure the wall mounting bracket to the structure
by using four fasteners (not provided).
6.2.3
Pendant mounting
F
The mounting type is for the use of bending tube
mounting (Figure 4).
F
Tube mounting thread is NPT 3/4”.
F
Thread the tube mounting on conduit and torque
until wrench-tight as requirement, 2700 kgf-cm.
6.2.4
Stanchion mounting 25°
F
The mounting types are for the use of bending
tube mounting (Figure 5). Tube mounting thread
is NPT 1-1/2”
F
Thread the tube mounting on conduit and torque
until wrench-tight as requirement, 6600 kgf-cm.
6.3 Ground wire
F
External earth screw location as showing in the
Red Circle of right pictures.
F
The external earth ground wire installation and
terminal type as show the right pictures.
F
Ground wire cross-sectional area=4mm²
,
max
LED current=1A; @V=110Vac-10%.
F
Both ground screw and washer material is
stainless steel.
F
Screw hole spec: M5.
F
Torque requirement: 14.5 kgf.cm.
F
Ensure wire is tied assured.
Figure 4