Copyright © 2014 by Thrush Co Inc
Section 4
Installation and Operation
4.1 Installation Tips
The following procedures are to aid the operator in installing the
Aar-O-Vent
. All
procedures are to be performed by experienced, trained, and certified personnel only.
5” and larger
Aar-O-Vents
have lift lugs to aid in lifting and locating the unit. The
lift lugs are not intended to be used to support the
Aar-O-Vent
during operation.
Adequately sized and spaced supports/hangers should be used to prevent
damage or strain on the system piping.
1. To protect the
Aar-O-Vent
during shipping, some of the components are shipped
unattached in protective packaging. These components are to be installed on site.
See Figure 3-1 for component locations.
2. The
Aar-O-Vent
should be located where it is easily accessible for inspection,
service and repair.
3. A standard
Aar-O-Vent
should be installed in-line in the system piping, in a
vertical position only. Adequately sized and spaced pipe supports/hangers should
be used to prevent damage or strain on the system piping.
4. An
Aar-O-Vent
should be installed in a piping system at its lowest point of
solubility. Typically the point of highest temperature and lowest pressure is the
ideal location.
5. When placing the
Aar-O-Vent
with removable head in the system piping, be aware
of the clearance required for bundle removal and cleaning. See Submittal Data for
distance required to remove bundle.
6. When piping the unit into system piping, the pipe should be sized to allow
adequate flow at a minimal head loss, and be, at minimum, the same size as the
Aar-O-Vent
connections. The use of elbows, tees or other restrictive fittings
should be kept to a minimum.
7. Isolation valves are recommended to allow gasket changes and inspection of the
bundle.
8. Expansion joints and or flex connectors are recommended to prevent pipe strain
caused by thermal expansion or piping misalignment.
9. System by-pass piping is also recommended to better facilitate system service
and maintenance.
10. The
Aar-O-Vent
will operate with flow entering the unit at either connection.
Thrush Co.
Manual #9636-1230
Содержание AAR-O-VENT TAHF