1.6
isNet H@rt+AI
The isNet H@rt8+AI module combines the HART master module with
4..20mA Analog Input functionality. The module provides 8 active AI
channels, which means the module will supply 24V DC to the HART
loops and thus power the connected HART instruments. The HART
instruments can be connected directly to the module, an external
loop resistor is not required as the input impedance of the AI chan-
nels already is 240 Ohms.
The measured analog values can be read by a connected PLC using
Modbus/TCP or Profinet. Due to the HART master functionality the
PLC has also access to the digital values of the HART instruments.
Additionally an engineering station can simultaneously access the
HART parameters of the connected HART instruments for configu-
ration, diagnosis or maintenance. This is possible with FDT based ap-
plications like PACTware, with OPC or with any other HART-IP client
applications.