1.  Installation

Prior to installation of the flow sensor, the system should be flushed.
Correct flow sensor position (flow or return) appears from the front label of 
MULTICAL®. The flow direction is indicated by an arrow on the side of the flow 
sensor.

Note

: ULTRAFLOW®

 

54 may be lifted in the lifting rings only.

Pressure stage ULTRAFLOW®

 

54

: PN25

Temperature of medium, ULTRAFLOW® 54

: 2…150°C/2…50°C.  

See marking on label.

Mechanical environment

: M1 and M2 (fixed installation with minimum vibration 

and fixed installation with considerable or high vibration level respectively). See 
marking on label.

Electromagnetic environment

 E1 and E2 (housing/light industry and industry 

respectively). See marking on label.
The meter’s signal cables must be drawn at min. 25 cm distance to other 
installations.

Climatic environment

: Can be installed in environments with non-condensing 

humidity as well as in closed locations (indoors).
The ambient temperature must be within 5…55°C.

Maintenance and repair

: The flow sensor is verified separately and can, therefore, 

be separated from the calculator. It is permitted to replace the supply and change 
the supply type. For battery supply a lithium battery with connector from Kamstrup 
A/S must be used. Lithium batteries must be correctly handled and disposed of 
(see Kamstrup document 5510-408, ”Lithium batteries - Handling and disposal”). 
Other repairs require subsequent reverification in an accredited laboratory.
If ULTRAFLOW® 54 is connected via a galvanically coupled output module, the flow 
sensor may be connected to a Kamstrup MULTICAL® calculator only.
If other calculator types are connected, ULTRAFLOW® 54 must be fitted with a 
galvanically separated output module and a power supply of its own.

Please note:

 Make sure that pulse figures of flow sensor and calculator are identical.

The steel tube between flow sensor housing and electronics box may not be 
disassembled.
At medium temperatures above 90°C (T

med

 > 90°C) or medium temperature 

more than 5°C below ambient temperature (T

med

 < T

amb

 - 5°C) the flow sensor's 

electronics box must be mounted via the enclosed distance piece. Alternatively, the 
electronics box can be wall mounted at a distance of minimum 170 mm from the 
sensor.
In order to prevent cavitation the back pressure at ULTRAFLOW® must be min. 1.5 
bar at q

p

 and min. 2.5 bar at q

s

. This applies to temperatures up to approx. 80

o

C.

When the installation has been completed, water flow can be turned on. The valve 
on the inlet side must be opened first.

Содержание Kamstrup ULTRAFLOW 54

Страница 1: ...Installation ULTRAFLOW 54 DN150 250 Tel 44 0 191 490 1547 Fax 44 0 191 477 5371 Email northernsales thorneandderrick co uk Website www heattracing co uk www thorneanderrick co uk...

Страница 2: ...2...

Страница 3: ...cal connection 11 2 1 Connection to calculator 11 2 1 1 ULTRAFLOW 54 and MULTICAL galvanically coupled 11 2 1 2 ULTRAFLOW 54 and MULTICAL galvanically separated 11 2 2 Connection of power supply 13 2...

Страница 4: ...4...

Страница 5: ...r battery supply a lithium battery with connector from Kamstrup A S must be used Lithium batteries must be correctly handled and disposed of see Kamstrup document 5510 408 Lithium batteries Handling a...

Страница 6: ...sor tube will thus be vertical which is optimal in connection with possible stratification of the medium Figure 1 1 1 1 Mounting ULTRAFLOW 54 in lifting ring ULTRAFLOW 54 can be mounted hanging from o...

Страница 7: ...the box approx 170 mm away from the flow sensor housing Alternatively a shorter distance piece which only moves the box approx 45 mm away from the flow sensor housing can be used The short distance p...

Страница 8: ...ays point downwards see paragraph 1 2 1 Orientation of flow sensor electronics box page 9 Alternatively the electronics box can be wall mounted as long as the distance to flow sensor housing and pipe...

Страница 9: ...the electronics box via the cables This is especially important in humid environments when ULTRAFLOW 54 is used as cooling sensor or if the medium temperature can become more than 5 C lower than the...

Страница 10: ...ceptable in closed systems Unacceptable position in open systems due to risk of air build up in system E A flow sensor ought not to be placed immediately after a valve with the exception of block valv...

Страница 11: ...nd MULTICAL are connected via output module Y 1 ULTRAFLOW 54 is galvanically coupled with the MULTICAL calculator and is powered by the calculator via the three wire signal cable cable length up to 10...

Страница 12: ...5 metres Diagram 3 Two wire connection MULTICAL 801 via output module Y 2 Cable length up to 100 metres Diagram 4 Two wire connection MULTICAL 602 D via output module Y 2 and external 24 VDC supply Ca...

Страница 13: ...laced by a corresponding lithium battery with connector from Kamstrup A S Used batteries must be handed in for approved destruction f inst at Kamstrup A S See Kamstrup document 5510 408 Lithium batter...

Страница 14: ...fixed 230 24 V installation in the main electrical panel must only be carried out by an authorized electrician Note This module cannot be supplied by 24 VDC direct current 230 24 V safety transformer...

Страница 15: ...company change Thus it can be an advantage to change mains supplied meters to battery meters in buildings under construction where the mains supply can be unstable or periodically missing Please note...

Страница 16: ...orward and return pipes are not necessarily closely coupled Electric welding can occur Electric welding must always be carried out with the earth pole closest to the welding point Damage to meters due...

Отзывы: