Assemble the product by sliding the body into place.
Secure the plate and body using the supplied screw.
Test The Luminaire
When the internal batteries have a period of time to charge, the test switch on the side of the luminaire
will allow you to spot check correct functionality. The charge indicator illuminates when in operation.
In accordance with the requirements of AS/NZS 2293, once the luminaire is installed and fully charged,
you will need to conduct a commissioning discharge test.
The Australian, New Zealand standards require newly installed emergency luminaires to operate in
emergency mode for 2 hours.
Subsequent maintenance testing is required every 6 months and testing is required to be recorded in
a suitable service logbook.