background image

W5003A

COMMISSIONING

WARNING:  230  Volts  is  present  on  the  underside  of  the 
printed circuit assembly.

Swivel  the  detector  head  to  give 

best coverage - by experimenting with various orientations, 
the range control can be kept to a minimum setting.

7.  With  the  room  empty,  ensure  that  there  are  no  spurious 

movement  signals  liable  to  cause  interference.    Check  this 
with  ventilation  and  other  machinery  running.    Possible 
interference  sources  are:  fans  turning,  flapping  notices, 
flashing fluorescent lights, running water etc.

Commissioning the photocell (if fitted):

8.   Set  switch  number  2  to  OFF.  Adjust  the  control  within  the 

photocell to a mid position.   This may be turned down to suit 
user requirements later.  (See photocell instructions.)

1. Set all mode switches to ON. 

2.  Adjust the timer controls to zero (fully anticlockwise). Relay 

R1 will time out in 4 seconds enabling the unit to be ‘walk 
tested’.

3.  Set both range controls fully anticlockwise. 

4.  Leave the area until the lights go off and then re-enter.

5.  Adjust the ON range control clockwise to increase sensitivity,                 

ensuring all areas are covered and that the lights are kept on 
with  minimal  movement. 

6.  Leave the area and wait for the lights to turn off. Wait a further 

10  seconds  then  re-enter.  Adjust  the  OFF  range  control 
clockwise  until  the  lights  are  switched  on  ONLY  AS  THE 
AREA IS ENTERED. 

*When set fully anticlockwise the OFF range is equal to 
the ON range.

 

Complete Commissioning

9.   Set the MODE switch to give the desired functions.  (See Modes 

of  Operation over.)

10. Set the OFF DELAY controls as required - each control has a 

range of 0 to 16 minutes.   A setting of around 5 - 10 minutes is 
usually appropriate.

Off Delay O/P1 relates to Relay R1.  (Off Delay O/P2 is not used). 

11. Lock the detector head into position before leaving (see detector 

instructions).

Switchlite

Installation &
Commissioning Instructions

Control Unit
SWITCHLITE HI-BAY MW CNTRL (96239719)

At the end of their useful life 
the packaging and product 
should be disposed of via a 
suitable recycling centre.
Do not dispose of with normal 
household waste.
Do not burn.

Thorn Lighting Limited
www.thornlighting.com

Отзывы: