Photocell

The photocell (SENSALINK SLOCSP only) can be programmed to operate in one of two ways: Active or 
Passive.  (Factory default setting is ‘Passive’.)

In all operating modes, the photocell can hold lights off as a vacant area becomes occupied, and if the light 
level falls too low during the period of occupancy, the lights switch on.  In ‘Passive Mode’ the lights do not 
switch off whilst the area is occupied no matter how much light is measured.  In ‘Active Mode’ the photocell is 
able to switch the lights off whilst the area is occupied.

Setting the Photocell 

1. If the lights are not already on, switch them on manually by pressing ‘Utilities/User Remote/Lu/OK’ 

[SENSALINK SENLP], or ‘Up’ [SENSA SENP]. Fluorescent lights do not reach full output until up to 15 
minutes after being switched on, so ensure that the lights are fully warmed up before continuing.  This stage 
may be omitted if the intention is to operate the detector’s photocell in Passive Mode only [the detector must 
have already been programmed to Passive Mode].

2. Wait until the time of day when the natural light level is at the point below which you 

would

 want the lights to 

be on, and above which you 

would not

 want the lights to be on.

3.  Start  the  internal  self-programming  mechanism  by  pressing  ‘Utilities/Set  Light  Level/OK’  [SENSALINK 

SENLP], or ‘Store’ [SENSA SENP].  The detector takes a measurement, adds a small amount and stores 
the value in the Upper Threshold.  Then it turns the lights off, makes another measurement and stores the 
value in the Lower Threshold.  The lights now switch on again to acknowledge a successful programming 
operation.

The two switching thresholds have now been set, and the difference between them is equal to the contribution 
made by the electric lighting; this is the perfect amount of hysteresis to ensure that the lights will not oscillate.  
The thresholds may be read back and fine-tuned if necessary using the SENSALINK SENLP.  Please note that 
the values are non-specific units i.e. not lux.

Note:

   The light level perceived by the detector at the moment immediately prior to a Download operation 

[SENSALINK SENLP only] is shown momentarily on the SENSALINK SENLP screen following the Download; 
this is a useful mechanism for troubleshooting.

Lights ON =

Lights OFF =

Upper Threshold

Lower Threshold

Natural
Light 
Level

Duration of 

Off Delay

Note that when the natural light 
level exceeds the ‘upper threshold’ 
value, the lights do not immediately 
turn off. They will turn off only when 
the upper threshold has been 
exceeded for the duration of the 
programmed Off Delay.

Active Mode

Passive Mode

Occupancy

Area Occupied =

Area Unoccupied =

- 6 -

Fig. 10

Содержание SensaLite SLOCS

Страница 1: ...tions SensaLite PIR Detector for Batten style Luminaires SENSALITE SLOCS Switching SENSALITE SLOCSP Switching with photocell SENSALITE SLOCS 96239752 SENSALITE SLOCSP 96239753 Note SENSALINK SENLP or...

Страница 2: ...Ensure that the tab is positioned correctly i e at the ceiling side away from the lamp 5 Fit and tighten the locknut 6 Connect the wires in accordance with the wiring instructions Polarising Plate no...

Страница 3: ...nected in parallel as is shown above to control the same Maximum Load L N E SUPPLY Maximum Total Load not to exceed that specified for a Single Detector LOAD LOAD L N E Fig 6 W5023A L N E L N E Always...

Страница 4: ...ape Diameter is 2 25 x the mounting height The squares show the arrangement of the detection pattern Fig 7 Direction of most commonly used entry into detection zone i e start of corridor or doorway Fi...

Страница 5: ...ds to allow the lights to switch off before moving and triggering the lights back on After 5 minutes the time out will be restored to what it was before walk test was enabled Notes on Walk Testing l D...

Страница 6: ...ternal self programming mechanism by pressing Utilities Set Light Level OK SENSALINK SENLP or Store SENSA SENP The detector takes a measurement adds a small amount and stores the value in the Upper Th...

Страница 7: ...mi automatic operation Photocell Operation Passive Active Disabled The SCLOCSP has an in built photocell The photocell has three modes of operation Passive Active and Disabled Its operational behaviou...

Страница 8: ...ype should be regarded as capable of maintaining an APPROXIMATE light level only 3 This equipment switches lights no more frequently than would a responsible human occupant However manufacturers of so...

Отзывы: