9.2 Precautions During Heavy Repair
Items
Precautions
Use of tools
Use special parts and tools for R134a,R600a
Removal of
retained refrigerant
1. Remove retained refrigerant more th an 5 m inutes after turning off a
refrigerator. (if not, oil will leak inside)
2. Remove retained refrigerant by cutting first high pressure side (dryer
part) with a nipper a nd then cut low pressure side.(if the order is n ot
observed, oil leak will happen)
Replacement of
dryer
Be sure to replace dryer when repairing pipes and injecting refrigerant.
Nitrogen bl owing
welding
Weld under nitrogen atmosphere in order to prevent oxidation inside a
pipe.
˄
Nitrogen pressure: 0.1~0.2 kg/cm2)
Others
1. Nitrogen only shou ld be used when cle aning inside of cy cle pip es
inside and sealing.
2. Check leakage with an electronic leakage tester.
3. Be sure to use a pipe cutter when cutting pipes.
4. Be careful not let the water intrude into the inside of the cycle
Dry filter
Solenoid valve
Refrigerator capillary
Freezer capillary
Hot pipe
Condensation tube
Freezer evaporator
Refrigerator evaporator
Compressor
58
Содержание HC-767
Страница 1: ...Repair Manual HC 767...
Страница 5: ...4 2 External Views 2 1 External Size Measurements in mm inches...
Страница 7: ...6 2 3 Cold air circulation...
Страница 20: ...T 50 58 T 50 122 T 50 58 T 50 122 T 50 58 T 50 122 3 seconds 3 seconds 3 seconds 3 seconds to close...
Страница 22: ...21 5 Wiring Diagram...
Страница 31: ...30...
Страница 32: ...31...
Страница 33: ...32...
Страница 34: ...33...
Страница 35: ...34...
Страница 36: ...35...
Страница 37: ...Fig 3 Fig 4 Check if voltage output or not UVW Anticlockwise Fig 3 Compressor terminal 36...
Страница 47: ...46...
Страница 49: ...Disassembly procedure of the right hinge cover and light switch is the same as the left 48...
Страница 65: ......