TSC 80 TRANSFER SWITCH CONTROLLER 

PM063  Rev 7  09/02/27 

 

 

Thomson Technology 

Voltage  sensing  circuits  are  capable  of  lethal  voltages  while 

energized.  Standard safety procedures should be followed and 

be performed by qualified personnel only.  Failure to do so may 

cause personnel injury and/or death. 

TB2-6  transfer  control  terminal  block  for  115VAC  control  power  and  input/output 

circuits. 

TB7 

low voltage (5Vdc) control inputs. 

2.2.2.  DIAGNOSTIC LED’S 

The  TSC  80  controller  provides  diagnostic  LED  lights,  which  are  mounted  on  the 

printed circuit board as per FIGURE 2. Their functions are described as follows: 

SYS OK 

This  LED  flashes  on  and  off  at  irregular  intervals,  which 

indicates the microprocessor is functioning normally. 

TRANSFER TO UTILITY This  LED  is  illuminated  whenever  the  TSC  80  is  initiating  a 

signal to transfer to the Utility supply. 

TRANSFER TO GEN  

This  LED  is  illuminated  whenever  the  TSC  80  is  initiating  a 

signal to transfer to the Generator supply. 

ENGINE STOP 

This LED is illuminated whenever the TSC 80 is initiating an 

Engine STOP signal. 

Содержание TSC 80

Страница 1: ...anada V1M 3B1 Telephone 604 888 0110 Telefax 604 888 3381 E Mail info thomsontechnology com www thomsontechnology com TSC 80 TRANSFER SWITCH CONTROLLER INSTALLATION OPERATING SERVICE MANUAL Software V...

Страница 2: ......

Страница 3: ...BOARD 8 2 2 1 TERMINAL BLOCKS 8 2 2 2 DIAGNOSTIC LED S 9 2 2 3 ADJUSTMENT POTENTIOMETERS 10 2 2 4 CONFIGURATION JUMPERS 10 2 3 TSC 80 CONTROLLER FEATURES 10 2 4 APPLICATION INFORMATION 11 2 4 1 AC VO...

Страница 4: ...URE 26 4 2 TSC 80 ADJUSTMENT POTENTIOMETERS 27 4 2 1 UTILITY UNDER VOLTAGE SETPOINT 28 4 2 2 GENERATOR UNDERVOLTAGE SETPOINT 29 4 2 3 GENERATOR UNDER FREQUENCY SETPOINT 29 4 2 4 ENGINE START DELAY 30...

Страница 5: ...08 08 14 Software updated to incorporate TSC 80e Option 2 1 09 01 01 Software updated to incorporate Configurable PT Ratio for TSC 80e Option 2 2 09 02 27 Software revised to correct 7 Day Genset Exer...

Страница 6: ...ite installation information consult Thomson Technology as required CAUTION contents subject to damage by STATIC ELECTRICITY This equipment contains static sensitive parts Please observe the following...

Страница 7: ...refer to electrical schematic confirm the transfer switch has been configured for the correct system voltage If the transfer switch requires reconfiguring the TSC 80 controller will require reconfigur...

Страница 8: ...rk performed must be done by qualified personnel only Failure to do so may cause personal injury or death 1 4 3 REMOTE START CONTACT FIELD WIRING As a minimum the remote engine start control field wir...

Страница 9: ...ing distance is excessively long i e greater than 100 feet 30m and or if a remote contact has a resistance of greater than 5 0 ohms 1 4 3 5 The remote start contact must be voltage free i e dry contac...

Страница 10: ...transfer switch door and a printed circuit board PCB which is mounted inside the transfer switch on the enclosure door 2 1 LEXAN FACEPLATES The TSC 80 Controller Lexan faceplate is shown as in FIGURE...

Страница 11: ...TSC 80 TRANSFER SWITCH CONTROLLER PM063 Rev 7 09 02 27 Thomson Technology 7 FIGURE 1 TSC 80 Controller Lexan Faceplate...

Страница 12: ...Return Neutral Delay Utility UV Gen Start Gen Cooldown TB1 TB7 JP5 SYS OK XFER UTIL XFER GEN LD ON GEN LD ON UTIL ENG STOP 29 37 PROG 2 PROG 3 PROG 1 TB6 TSC 80e ONLY BT1 REAL TIME CLOCK BATTERY TSC8...

Страница 13: ...2 DIAGNOSTIC LED S The TSC 80 controller provides diagnostic LED lights which are mounted on the printed circuit board as per FIGURE 2 Their functions are described as follows SYS OK This LED flashes...

Страница 14: ...roprocessor technology printed circuit board assembly and software for control of automatic transfer switches The TSC 80 is the second generation of microprocessor based transfer switch controllers fr...

Страница 15: ...resistive max Load on utility auxiliary contact Qty 1 only 10A 120 240VAC Form C Load on generator auxiliary contact Qty 1 only 10A 120 240VAC Form C Transfer fail forced transfer logic Automatic for...

Страница 16: ...ONLY TSC 80 TSC 80e L2 L1 N 1 2 3 10 25 24 GRD GRD 26 NO CONNECTION 1 3W 120 240VAC DIRECT SENSING 1 2 3 25 26 24 NOTE UTILITY VOLTAGE SENSING AND CONTROL POWER SHOWN ONLY B A C N GRD GRD 120V NOTE F...

Страница 17: ...tings i e 10A resistive 120VAC Total AC control power requirements for each supply must be determined by adding both internal and external load requirements 2 4 3 OUTPUTS The TSC 80 provides the follo...

Страница 18: ...y rises above preset values 70 95 nominal adjustable the Engine Warm up timer will be initiated Once the Engine Warm up timer expires 0 60 sec Adjustable the transfer to generator supply signal contac...

Страница 19: ...tor supply i e when both sources of power are available The transfer switch shall remain on generator supply until the test mode is terminated It will then retransfer back to the utility supply follow...

Страница 20: ...rm is initiated Load Source Flashing LED after 11 second delay then a forced transfer to the alternate source is initiated Re transfer back to the original source will not occur until the Transfer Fai...

Страница 21: ...er 10 sec Find Neutral Source Timer 10 sec Limit Switch Failure Loss of Load Voltage 80VAC 31 seconds 3 1 2 6 SERVICE ENTRANCE ATS For Service Entrance Rated transfer switch applications the transfer...

Страница 22: ...Once the mode is initiated the engine will immediately start and transfer on load i e if configured for On Load Test once nominal voltage and frequency levels have been obtained The engine will remain...

Страница 23: ...use of the faceplate mounted pushbuttons NOTE When an external FTS4 switch is used the TSC 80 operation as selected from the faceplate pushbuttons will be overridden OFF Disables the engine start out...

Страница 24: ...tor supply When the remote contact is opened the load will re transfer back to the utility supply following expiry of the Utility Return delay timer The Engine Cooldown time sequence will be initiated...

Страница 25: ...test is held on for longer than 5 seconds 3 5 TIMER BYPASS To bypass an active timing sequence e g utility return timer cooldown timer warm up timer during operation both Lexan faceplate pushbuttons...

Страница 26: ...g 4 1 CONFIGURATION JUMPERS The following configuration jumpers are provided on the printed circuit board to program the TSC 80 controller WARNING The configuration jumper settings must not be changed...

Страница 27: ...ns contact Thomson Technology for further information 4 If multiple jumpers are incorrectly left on the voltage selection pins the highest voltage selected will have precedence When a system voltage i...

Страница 28: ...e for typical 85 drop out under voltage setpoints System Voltage ATS Transformer Tap Setting TSC 80 Voltage Jumper Setting 85 Drop out Voltage TSC 80 Under voltage Potentiometer Setting 208V 208V tap...

Страница 29: ...e placed across the 2 pins adjacent to the text on the PCB When a system frequency is selected the TSC 80 s generator frequency setpoint percentage setting will be automatically programmed to correspo...

Страница 30: ...oad Test mode is the factory default setting No Load Gen Exercise Test Mode program jumper is required to be placed across the 2 pins adjacent to the text on the PCB NOTE Should utility power fail dur...

Страница 31: ...by pressing the Test pushbutton for 5 seconds NOTE When a configuration jumper is not required the jumper should be connected to only one pin of the header to conveniently store it for future use 4 2...

Страница 32: ...ting is expressed in percentage of system voltage setting with an adjustable range of 70 95 e g If system voltage configuration jumper is set for 600V an 80 under voltage setting will correspond to an...

Страница 33: ...ng i e nominal system voltage and the potentiometer setting Actual system operating voltage should not be used to calculate the under voltage setpoint The under voltage setting is for a falling genera...

Страница 34: ...i e differential value Example if under frequency is adjusted to an 80 drop out value i e 48 0Hz it will reset at 48 3Hz The 0 5 differential value is not programmable NOTE To override momentary under...

Страница 35: ...oldown Delay timer 4 2 7 UTILITY RETURN DELAY A potentiometer is provided to adjust the TSC 80 s Utility Return Delay timer The Utility Return delay period will be initiated once the utility supply ha...

Страница 36: ...L2 8 19 20 25 L LOAD ON UTILITY SUPPLY INPUT 120VAC TRANSFER TO UTILITY OUTPUT RATED 10A 120 250VAC 10A 30VDC RES MAX LOAD ON GENERATOR SUPPLY INPUT 120VAC 28 27 ENGINE START CONTACT Contact closes to...

Страница 37: ...nal no external load connected VOLTAGE SENSING Direct 120 600VAC nominal single or 3 phase 50 60Hz 1 0 accuracy of setting 25 C OPERATING TEMPERATURE 40 C to 50 C TSC 80 OUTPUT CONTACTS Form C 10A 120...

Страница 38: ...to isolate the transfer switch from any possible source of power Failure to do so may result in serious personal injury or death due to electrical shock Service procedures must be undertaken by qualif...

Страница 39: ...rvice Entrance type ATS and TSC 80 Transfer Fail alarm activated Determine cause of alarm and rectify before TSC 80 is reset Generator does not start up or stop when it should Verify remote engine con...

Страница 40: ...TSC 80 printed circuit board If the TSC 80 controller is deemed to be defective it must be returned to the Thomson Technology Factory for repair or replacement Please refer to SECTION 9 for further de...

Страница 41: ..._____________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________...

Отзывы: