![THOMSON TS 840 Скачать руководство пользователя страница 32](http://html.mh-extra.com/html/thomson/ts-840/ts-840_service-manual_1110068032.webp)
TS 840 TRANSFER SWITCH
PM057 REV 8 10/01/25
28
Thomson Technology
determined. The grounding points of the system shall be verified to determine that ground
paths do not exist that would bypass the sensors. The use of high-voltage testers and
resistance bridges may be required. A simulated fault current is to be generated by a coil
around the sensors. The reaction of the circuit-interrupting device is to be observed for
correct response. The results of the test are to be recorded on the test form provided.
Содержание TS 840
Страница 2: ......
Страница 37: ...TS 840 TRANSFER SWITCH PM057 REV 8 10 01 25 33 Thomson Technology 19 NOTES ...