4.6.10 Control option LXP
In addition to all of the features included in the LXX version (section 4.6.8), LXP also includes a
potentiometer providing a voltage signal for the customer to use to determine position, speed and
direction.
Power the actuator by connecting red to + Vdc and black to - Vdc in the power cable. To extend the
actuator apply +Vdc to violet and to retract apply +Vdc to orange in the signal cable while applying -Vdc
to grey.
F Fuse
S1 Extend switch
S2 Retract switch
LXP Control Option Specifications
Input voltage
MD12
MD24
[Vdc]
9 - 16
18 - 32
Max. actuator current draw [A] see product label
Potentiometer type
wirewound
Potentiometer max.
input voltage
[Vdc]
32
Potentiometer max.
power
[W]
1
Potentiometer linearity
[%]
± 0.25
Potentiometer output
resolution
[ohm/mm]
MDxxA025, all strokes
MDxxA100, all strokes
MDxxA050, 50 - 250 mm stroke
MDxxA200, 50 - 250 mm stroke
MDxxA050, 300 mm stroke
MDxxA200, 300 mm stroke
16.67
16.67
33.33
33.33
16.67
16.67
Extend / retract input voltage [Vdc]
9 - 32
Extend / retract input current [mA]
6 - 22
not used
not used
ext/ret + Vdc
- Vdc
pot. + Vdc
pot. - Vdc
pot. output
red
black
white
blue
orange
violet
brown
grey
red/white
black/white