Emergency LED Battery Pack Installation,
Operation, and Service Instructions
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should
always be followed including the following.
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. Do not join converter connection until installation is complete and AC power is supplied to the emergency
driver.
2.
This product is for use with an emergency LED lighting load and supplies 7 W of constant output power to
LED lamps rated from 15-56 Vdc. Operates emergency LED load in the emergency mode for a
minimum of 90 minutes.
3. Make sure all connections are in accordance with the NEC and any local regulations.
4. To reduce the risk of electric shock, disconnect both normal and emergency power supplies and converter
connector from the emergency driver before servicing.
5. This emergency driver is suitable for factory or field installation.
6.
Do not use outdoors.
This product is suitable for use in damp locations where the ambient temperature is
7. An unswitched AC power source is required (120-277 VAC, 50/60 Hz).
8. Do not install near gas or electric heaters.
9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable.
Contact
T
homas
R
esearch
P
roducts
for information on service.
10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
11. Do not use this product for other than intended use.
12. Servicing should be performed by qualified service personnel.
13. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by
unauthorized personnel
SAVE THESE INSTRUCTIONS
WARNING
-
This product contains chemicals known to the State of California to cause cancer,
birth defects, and/or other reproductive harm. Thoroughly wash hands after installing, cleaning, or
otherwise touching this product.
CAUTION: DISCONNECT POWER DURING INSTALLATION AND BEFORE SERVICING.
READ ALL INSTRUCTIONS COMPLETELY BEFORE STARTING INSTALLATION.
SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS
SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT
ALB
ALB
EC-161212009
12/20/16
1
4
3
D
C
B
A
4
3
2
1
D
C
B
A
1
2
REV
DATE
RECORD
DESN CHCK
SHT 1
1 SHTS
---
---
93079821
93079821
1
ILL-PLD10M
ALB
12/20/16
ALB
12/20/16
---
ALB
12/20/16
NTS
REV.
DRAWING NO.
SIZE
SCALE
PART NO.
FINISH:
MATERIAL:
This document contains confidential and proprietary information of Dual
Lite. Receipt or possession of this document does not convey any rights to
reproduce or disclose its contents, or to make, use , or sell anything it may
disclose. Reproduction, disclosure, or use of the document or its contents,
without the specific written authorization of Dual Lite, may violate the
intellectual property rights of Dual Lite.
DIMENSIONS IN INCHES
DIMENSIONS IN [ ] IN MM
CONFORMS TO ASME Y14.5M
DO NOT SCALE PRINT
DRAWN BY:
THIRD ANGLE PROJECTION
CHECKED BY:
ENGINEERING:
CATALOG NO.
CRITICAL DIMENSIONS
C
UNSPECIFIED TOLERANCES: INCHES
X.XX=
u
0.12
FRACTIONS=
u
1/32 ANGULAR TOLERANCE=
u
1
v
THIS ILL IS USED ON INSTRUCTION SHEET 93078192
LBU7-M
/
LBU7-
M2
INSTALLER:
P/N:930
57557
LBU7-
M2
CLASS 2 OUTPUT
0
°C minimum, +55°C maximum. Product is not suitable for heated air outlets and wet
or hazardous locations.
E491125
P/N:93057556 LBU7-M