Revision A
June 2009
9
The menu is arranged as follows:
Display
Modifiable
Description
*Port Power
Port 1
Yes
Displays status of power on Port 1
Port 2
Yes
Displays status of power on Port 2
Port 3
Yes
Displays status of power on Port 3
Port 4
Yes
Displays status of power on Port 4
Port 5
Yes
Displays status of power on Port 5
Port 6
Yes
Displays status of power on Port 6
Port 7
Yes
Displays status of power on Port 7
Port 8
Yes
Displays status of power on Port 8
Display
Modifiable
Description
*System
DAISY Position
No
Location in DAISY Chain
Ctrl Rev
No
Revision of PDU
Offset Current (Tare) Yes
Calibrate current monitor on all ports.
Debug Values
Yes
Factory Debug Facility
Offset Current Tare is only available from the front panel. This menu option sets a zero current
reference and stores it in non-volatile memory. To use this feature all ports must be off. Once
ports are off, set the Offset Current Tare to Yes, it will revert back to No when the calibration is
complete.
Rear Panel View
The rear panel consists of (2) Power Cords, (2) Circuit Breakers, (8) AC Power Outlets, (8) Port
Status LEDs, (1) USB Firmware Upgrade Port, and (2) Console Ports.
Power Connections
The rear panel consists of two Banks: Bank 1 and Bank 2. Each Bank consists of (1) AC Input
Power Cord, (1) Power Switch/Circuit Breaker, and (4) AC Power Outlets.
Bank 1 provides AC power for Ports 1 through 4 and AC/DC Power Supply 1;
Bank 2 provides AC power for Ports 5 through 8 and AC/DC Power Supply 2.
CONTROL IN
CONTROL OUT
F
IR
M
W
A
R
E
U
P
G
R
A
D
E
1
4
3
2
5
6
7
8
BANK 1
1
2
4
3
BANK 1
BREAKER
BANK 1
SUPPLY
115 VAC 60HZ
15 AMPS
BANK 2
5
6
8
7
BANK 2
BREAKER
BANK 2
SUPPLY
115 VAC 60HZ
15 AMPS