2.3 Do not OVERLOAD the phase-converter

Overloading a phase-converter above its rated capacity can damage the phase-
converter and the connected electrical devices. Respect the following instructions
to avoid overloading the unit:

- Calculate the total HP of all the electrical devices to be connected at the same
time. The total must not exceed the phase-converter's capacity (see section 3).
- Identify the HP of the most powerful motor and ensure it does not exceed the
phase-converter's capacity (see section 3).
- If the phase-converter is connected to resistive loads (heating or a welding
machine):

1- Determine the current (amperage) used by the equipment
2- Multiply this number by the operating voltage to get the Watts

    

    (volts x   amperes = watts)
3- Multiply the Watts x 1.5 and then ensure it does not exceed

               the equipment's capacity (see section 3)

3 Technical specifications of the products

3.1 Current (amperage) of the phase-converters at full capacity (100%)

Model

Single-phase

input (A)

Three-phase

output (A)

Start-up (A)

MT-3

15

9

25

MT-6

22

13

44

MT-9

40

23

58

MT-12

50

30

72

MT-15

65

38

92

MT-21

90

53

140

MT-30

130

76

183

MT-45

200

115

288

MT-60

260

153

360

MT-75

330

191

420

Содержание Multi Phases MT-12

Страница 1: ...Manufactured by Thetford Armature Inc...

Страница 2: ...1 2 Connecting the device 3 2 Usage 5 2 1 Starting up the phase converter 5 2 2 Operating the phase converter 5 2 3 Do not OVERLOAD the phase converter 6 3 Technical specifications of the products 6...

Страница 3: ...hase converter the WARNING block is used to alert employees of special instructions concerning specific operations that could prove hazardous if not executed properly or with caution The operator is r...

Страница 4: ...of the single phase power supply respectively to A and B terminals of the junction box C Connect the phase converter s T1 T2 and T3 terminals see Figure 2 respectively to the A B and C terminals of t...

Страница 5: ...ar transformer WARNING NEVER CONNECT THE H0 or X0 OF A TRANSFORMER S PRIMARY TO THIS EQUIPMENT When using an autotransformer the neutral H0 or X0 must never be connected to the phase converter When us...

Страница 6: ...so it is recommended to start them no more than once or twice a day WARNING Always start up the phase converter by itself without any load Always ensure that the input voltage loss is not greater tha...

Страница 7: ...nverter s capacity see section 3 If the phase converter is connected to resistive loads heating or a welding machine 1 Determine the current amperage used by the equipment 2 Multiply this number by th...

Страница 8: ...Total Watts Max Watts Total MT 3 1 3 746 2 240 MT 6 2 6 1 500 4 500 MT 9 3 9 2 250 6 700 MT 12 4 12 3 000 9 000 MT 15 5 15 3 700 11 100 MT 21 7 5 21 5 600 16 800 MT 30 10 30 7 500 22 400 MT 45 15 45 1...

Страница 9: ...Multi Phases does not comply with the terms of the warranty the buyer may aside from any other procedure return it to Thetford Armature Inc at the address below postage and insurance paid Thetford Arm...

Страница 10: ...incidental or consequential costs expenses or damages will not be affected by any breach of the essential purpose of this limited warranty Thetford Armature Inc 1224 rue du Parc Thetford Mines G6H 2N...

Отзывы: