Multi-Phases
6
2.3 Do not OVERLOAD the phase-converter
Overloading a phase-converter above its rated capacity can damage the phase-
converter and the connected electrical devices. Respect the following instructions
to avoid overloading the unit:
- Calculate the total HP of all the electrical devices to be connected at the same
time. The total must not exceed the phase-converter's capacity (see section 3).
- Identify the HP of the most powerful motor and ensure it does not exceed the
phase-converter's capacity (see section 3).
- If the phase-converter is connected to resistive loads (heating or a welding
machine):
1- Determine the current (amperage) used by the equipment
2- Multiply this number by the operating voltage to get the Watts
(volts x amperes = watts)
3- Multiply the Watts x 1.5 and then ensure it does not exceed
the equipment's capacity (see section 3)
3 Technical specifications of the products
3.1 Current (amperage) of the phase-converters at full capacity (100%)
Model
Single-phase
input (A)
Three-phase
output (A)
Start-up (A)
MT-3
15
9
25
MT-6
22
13
44
MT-9
40
23
58
MT-12
50
30
72
MT-15
65
38
92
MT-21
90
53
140
MT-30
130
76
183
MT-45
200
115
288
MT-60
260
153
360
MT-75
330
191
420