55
Explanation for 4 X register :
Address Parameter
40003 Output Mode
Selection
This is used to select the
ode
By setting output in simulation mode user
can simulate the output variation without
giving input. Normal mode = 1.
Simulation mode = 2.
output m
.
Description
This is used to select the
For Apparent / Active / Reactive Power
Transducer
1) 3 Phase 3 wire unbalanced = 3.
2) 3 Phase 4 wire unbalanced = 4.
3) Single Phase = 1.
4) 3 Phase 4 wire balanced = 8.
5) 3 Phase 3 wire balanced = 2.
For Phase Angle or Power Factor Transducer
1) U12 I1( 3 Phase 3 wire balanced) = 5.
2) U23 I1 ( 3 Phase 3 wire balanced) = 6.
3) U31 I1 ( 3 Phase 3 wire balanced) = 7.
system type.
40005
System Type
Note:
After power ON / OFF Transducer
goes to normal mode
Address
(Register)
Parameter
No.
Parameter
Modbus Start Address Hex
Low Byte
High Byte
Read / Write
40027
14
Sim_Output A
Wp
40029
15
Sim_Output B
Wp
40031
16
Analog O/P Type 1
R/Wp
00
00
00
00
00
1A
1C
1E
40033
17
00
R/Wp
20
Output para select 1
40035
18
Analog O/P Type 2
R/Wp
00
22
40041
19
00
R/Wp
28
Diagonsis Mode