BOILER MOUNTING
9
3.2.2.
Boiler room dimensions
The boiler must be placed on a horizontal plane, with adequate mechanical resistance to
support the boiler’s weight. The boiler must be positioned in the room in such a way so that it
is easily accessible from all the sides. The following dimensions are recommended (see Fig 2):
Distance from the front wall (N):
For boilers up to 100 kW
–
minimum 1,5 m
For boilers bigger than 100 kW
–
minimum 2 m
Distance from the rear wall (L):
Appropriate distance for maintenance access. Minimum 0,6 m.
Distance from side walls (M):
For boiler up to 300 KW
–
minimum 0,6 m
For boilers bigger than 300 kW
–
minimum 1 m
Boiler room height (H):
For boilers up to 70 kW
–
minimum 2 m
For boilers 70 to 230 kW
–
minimum 2,4 m
For boiler 230 to 400 kW
–
minimum 3 m
For boiler bigger than 400 kW
–
minimum 3,5 m
Distance between two boilers (P) must be at least 1m.
Fig 2.
Recommended boiler room dimensions