Page 7 of 26 

150mm 
minimum clearance 

COOL   AIR 

White unit shown for picture clarity only 

INSTALLING THE DRY COOLING UNIT

 

The dry cooling unit has been designed to be mounted on a wall or suspended from 
above using M10 drop rods. It must not be installed on the outside of the building, 
or built into a cabinet or recessed in anyway.

 

 Location 

The dry cooling unit must be mounted so the unit is 
horizontal and 

level

 and the discharge grille faces 

downwards. The discharge grille must be at least 
2.4m above ground level and located so the 
downwards flowing cool air will distribute throughout 
the room or across equipment to be cooled. It 
should not, however, be positioned directly above 
valuable or delicate equipment in case of water 
leaks or an emergency condensate situation, e.g. 
doors left open, extreme weather conditions. 
Beware of obstructions in the room that may 
interfere with air distribution. Leave a gap of 150mm 
minimum above the unit to allow for installing the water pipework. 

 

 Wall Fixing 

There are three wall brackets supplied and these need to 
be bolted to the rear face of the cooling unit as shown in 
the adjacent picture using the M10 bolts supplied. A 
suitable wall fixing system (not supplied) needs to be 
used to fix the brackets to the wall, taking into account the 
type of wall and the weight of the unit  -  76kg.* 

Step 1.

 Refer to Figure 1, Page 8 for mounting details 

and drill the fixing points in the wall. 

Step 2.

 Screw in the top wall bolts leaving a small gap 

between the bolt head and the wall. Lower the cooling 
unit onto the bolts via the key-hole slots in the top of the 
wall brackets and then screw in the bottom wall bolts. 

Step 3

. Ensure all fixing bolts are tightened and the dry 

cooling unit is safely secured to the wall. 

  Ceiling Suspension 

There are six M10 threaded inserts provided in the top 
face of the cooling unit (see Figure 1, Page 8 for 
positions) so it can be suspended on M10 threaded 
hanging rods with lock nuts (not provided). All six 
suspension points must be used. Ensure each of the 
hanging rods is secured onto a suitable structure that can 
support the weight of the unit  -  76kg.* Screw the M10 
hanging rods into the threaded inserts by a minimum of 
20mm and fit locking nuts to prevent the rod rotating and 
coming away from the casing. Do not screw the hanging 
rods too far in or they could interfere with internal 
components. 

 

*

 It is the sole responsibility of the installer to ensure that 

the building fixing locations and suspension system used 
are suitable for the dry cooling unit being installed.

 

White unit shown for picture clarity only 

Содержание PHV2000NT

Страница 1: ...NCE INSTRUCTIONS For use with PUHZ HW140VHA2 or YHA2 Outdoor Units PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING INSTALLATION Thermoscreens Ltd St Mary s Road Nuneaton Warwickshire Englan...

Страница 2: ...allation items supplied and fitted by installer Thermoscreens PHV2000NT Dry Cooling Unit Mitsubishi Electric PUHZ HW140 Outdoor Unit Permanent 1 phase mains electrical supply Siemens RDG400 Manual Roo...

Страница 3: ...sed unvented water system must be used for the flow and return water pipework between the Thermoscreens dry cooling unit and the Mitsubishi Electric outdoor unit This should incorporate water pump s e...

Страница 4: ...his should be connected to the 15mm copper drain pipe that protrudes from the right hand rear of the cooling unit behind the plastic end cap Condensate pumps are not recommended but if a gravity drain...

Страница 5: ...is to provide warning of elevated room air temperatures which could indicate a fault in the air conditioning system or some other problem This thermostat can be set during commissioning to between 15...

Страница 6: ...chase is necessary so please keep a copy of your invoice IMPORTANT This Dry Cooling Unit is intended only for use with a Mitsubishi Electric PUHZ HW140VHA2 or YHA2 Air to Water Outdoor Unit These inst...

Страница 7: ...fixing system not supplied needs to be used to fix the brackets to the wall taking into account the type of wall and the weight of the unit 76kg Step 1 Refer to Figure 1 Page 8 for mounting details an...

Страница 8: ...c 150 min 6 x M10 threaded holes for M10 drop rods IMPORTANT Use all 6 drop rod holes 3 Holes x 20mm Water Connections Rp1 56 70 1in BSP Internal Emergency Condensate Connection at rear of plastic end...

Страница 9: ...ure plus two in the centre and pull the panel out forwards Chilled Water Pipework Left hand side of unit This should ideally be carried out before connection of any electrical and controls cables The...

Страница 10: ...nal pipework if used must be weather wrapped or installed in suitable trunking Condensate Disposal System Right hand side of unit As explained in Section Design Information Page 3 the dry cooling unit...

Страница 11: ...l accept a 10mm diameter condensate sensor Different size grommets can be fitted to suit other condensate sensors or if the grommet is removed a larger condensate sensor can be located in the 13mm dia...

Страница 12: ...Power Input kW rating of water pump installed 2 7A for cooling unit Rated Current Amps of water pump installed max 2A IMPORTANT Please note that the water pump is supplied and fitted by the installer...

Страница 13: ...TB62 5 6 A B Brown Blue PUHZ HW140VHA2 YHA2 Unit Error Signal Volt Free Output FAN MOTORS SIEMENS RDG400 MANUAL ROOM CONTROL CN20 RED Link Fitted L2 L1 N E CNS2 Mitsubishi sensor fitted in pocket of f...

Страница 14: ...onnection 8 Mitsubishi Electric heat pump system Error Signal volt free contacts rated 1A max Error Closed 9 Terminal on Dry Cooling Unit Optional Room Over Temperature Alarm Volt Free contacts rated...

Страница 15: ...picture NB For clarity the site wiring to terminals 6 to 12 for the optional items Remote ON OFF Mitsubishi Error Signal Room Over Temperature Alarm is not shown in this picture Please note All the pa...

Страница 16: ...nstallation debris is removed see BSRIA AG 1 2001 1 Check that the chilled water system has been filled and the correct concentration of inhibitor has been added If necessary check that the system has...

Страница 17: ...there is site wiring between terminals 4 5 in the dry cooling unit and terminals M B1 in the Siemens RDG400 manual room control the room air temperature will be measured using the black return air tem...

Страница 18: ...k there is no mechanical noise coming from the fans and that both fans work If there is a Remote On Off wired into terminals 6 7 on the dry cooling unit switch this On Check that the LCD display scree...

Страница 19: ...condensate pump is being used ensure this is operating correctly and if possible simulate a pump alarm fault condition to check that the alarm will function Some condensate pumps may require distilled...

Страница 20: ...ill then flash this target temperature 5 times and go back to showing the air temperature If the target temperature is lower than the air temperature the outdoor unit and the water pump s will start t...

Страница 21: ...Always disconnect and isolate the mains electricity supply both at the local electrical supply to the Thermoscreens Dry Cooling Unit and at the Mitsubishi Electric Outdoor Unit before servicing maint...

Страница 22: ...ituation It may be that there has been a failure in the air conditioning on site or environmental conditions in the server room have gone above 24 C 40 Rh due to some other circumstance e g doors left...

Страница 23: ...ns dry cooling unit using a damp cloth Do not use scouring cream products Visually inspect the pipe work system for water leaks and repair as necessary Check the condition of the pipework insulation a...

Страница 24: ...temperature down NB Dry cooling unit will only cool if room air temperature is above the target temperature Room temperature is low Air Inlet Sensor is measuring low air temperature so target tempera...

Страница 25: ...re they are correct although Thermoscreens Ltd disclaims all liability for damage resulting from any inaccuracies and or deficiencies in this documentation Thermoscreens Ltd retain the right to change...

Страница 26: ...Series Type PHV2000 NT used with Mitsubishi Electric PUHZ HW140VHA YHA VRF PHV2000 NT used with Mitsubishi Electric PWFY P200VM E AU Relevant EC Council the Machinery Directive 2006 42 EC the Low Vol...

Отзывы: