![Thermoscreens HP1000 DXE Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/thermoscreens/hp1000-dxe/hp1000-dxe_installation-operation-and-maintenance-instructions-manual_1106177003.webp)
T9901085-1-3 UK
Page 3 of 38
Thermoscreens / Mitsubishi Electric
Mr Slim HP Heat Pump Air Curtain System
with
Weather Compensation Control
or
Discharge Air Temperature Control)
Air Curtain is supplied set-up to operate on either of these control modes
The Mr Slim HP Heat Pump Air Curtain System consists of :-
a Thermoscreens 'HP Air Curtain' fitted with a Mitsubishi Electric PAC-IF010B-E
Interface PCB, with dip switches set to be a PAC-IF020B-E *
a Mitsubishi Electric 'Mr Slim Outdoor Unit'
+
a Mitsubishi Electric 'PAR-W21 MAA Remote Controller' for manual control by the
occupant of weather compensation control or discharge air temperature control
+
a door switch to change fan speeds; higher speed when the door is open, lower speed
when the door is shut
^
a Thermoscreens ‘Remote 3-Speed Fan Switch’ (if end user requires this) *
* - supplied by Thermoscreens Ltd.
+
- Mitsubishi Electric items supplied by the installer
^
- supplied by the installer
Refrigeration pipework
Electrical cables
Control cables
BMS Control
Heat Pump
Air Curtain
Mitsubishi Electric
Mr Slim Outdoor Unit
S2, S3 communication
link with outdoor unit
Permanent electrical supply (from local switched spur)
1-phase for air curtain as supplied,
3-phase only if defrost cycle auxiliary heater is needed
(site change then required to air curtain)
(S1 is not used)
Permanent electrical supply
(from local switched spur)
Mitsubishi Electric
PAR-W21 MAA
Remote Controller
Optional
BMS Control
Interface Board
On/Off
Mode change
Weather compensation
control or Discharge air
temp. control
Mitsubishi error
BMS
Control
Remote
3-Speed Fan
Switch
(if end user
requires this)
Door Switch to change fan speeds,
Door open - High; Door shut - Low
(industry standard fan speed control)